    Release date  2012-07-06 08:53 Date of issue  2012-07-17 132960_eng.xml
    KFD2-SR2-Ex2.W
    Subject to reasonable modifications due to technical advances.  Copyright Pepperl+Fuchs, Printed in Germany
    Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 1
    Switch Amplifier
    2+
    3-1+
    Zone 2
    Div. 2
    Zone 0, 1, 2
    Div. 1, 2
    KFD2-SR2-Ex2.W
    7
    8
    9
    10
    11
    12
    I
    II
    I
    II
    24 V DC
    14+
    15-Power Rail
    24 V DC ERR
    5+
    6-4+
    10 kΩ
    10 kΩ
    400  Ω ≤ R ≤ 2 k Ω
    10 kΩ
    10 kΩ
    400  Ω ≤ R ≤ 2 k Ω
    Connection
    Assembly
    • 2-channel isolated barrier
    • 24 V DC supply (Power Rail)
    • Dry contact or NAMUR bs
    • Relay contact output
    • Line fault detection (LFD)
    • Reversible mode of operation
    • Up to SIL2 acc. to IEC 61508
    Function
    This isolated barrier is used for  intrinsic safety applications. It
    transfers digital signals (NAMUR sensors/mechanical
    contacts) from a hazardous area to a safe area.
    The proximity sensor or switch controls a b C changeover
    relay contact for the safe area load. The normal output state
    can be reversed using switches S1 and S2. Switch S3 is used
    to enable or disable line fault  detection of the field circuit.
    During an error condition, the relays revert to their de-energized state and the LEDs in dicate the fault according to
    NAMUR NE44.
    A unique collective error messaging feature is available when
    used with the Power Rail system.
    Features
    1 3
    4 6
    2
    5
    13 15
    12
    9
    10
    7
    14
    11
    8
    KFD2-SR2-Ex2.W
    1
    2
    OUT CHK PWR
    S2
    S1
    S3
    II I
    Front view
    LED yellow:
    Relay output  Ι
    LED red:
    LB/SC channel  Ι
    LED yellow:
    Relay output  ΙΙ
    LED red:
    LB/SC channel  ΙΙ
    Switch S3
    (LB/SC-monitoring)
    LED green:
    Power supply
    Removable terminals
    green
    Removable terminals
    blue
    Switch S1
    (Mode of operation channel  Ι)
    Switch S2
    (Mode of operation channel  ΙΙ )
    2
    Release date  2012-07-06 08:53 Date of issue  2012-07-17 132960_eng.xml
    Technical data KFD2-SR2-Ex2.W
    Subject to reasonable modifications due to technical advances.  Copyright Pepperl+Fuchs, Printed in Germany
    Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 2
    General specifications
    Signal type  Digital Input
    Supply
    Connection  Power Rail or terminals 14+, 15-Rated voltage  20 ... 30 V DC
    Ripple  ≤  10  %
    Rated current  ≤  50 mA
    Power loss  1 W
    Power consumption  < 1.3 W
    Input
    Connection  terminals 1+, 2+, 3-; 4+, 5+, 6-Rated values  acc. to EN 60947-5-6 (NAMUR)
    Open circuit voltage/short-circuit current  approx. 8 V DC / approx. 8 mA
    Switching point/switching hysteresis  1.2 ... 2.1 mA / approx. 0.2 mA
    Line fault detection  breakage I  ≤ 0.1 mA , short-circuit I > 6 mA
    Pulse/Pause ratio  ≥  20 ms /  ≥  20 ms
    Output
    Connection  output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
    Output I, II  signal, relay
    Minimum switch current  2 mA / 24 V DC
    Energized/De-energized delay  approx. 20 ms / approx. 20 ms
    Mechanical life  10
    7
     switching cycles
    Transfer characteristics
    Switching frequency  ≤  10 Hz
    Electrical isolation
    Input/Output  reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
    eff
    Input/power supply  reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
    eff
    Output/power supply  reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
    eff
    Output/Output  reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
    eff
    Directive conbity
    Electromagnetic compatibility  
    Directive 2004/108/EC  EN 61326-1:2006
    Low voltage  
    Directive 2006/95/EC  EN 61010-1:2010
    Conbity
    Electromagnetic compatibility  NE 21:2006
    Protection degree  IEC 60529:2001
    Input EN 60947-5-6:2000
    Ambient conditions
    Ambient temperature  -20 ... 60 °C (-4 ... 140 °F)
    Mechanical specifications
    Protection degree  IP20
    Mass  approx. 150 g
    Dimensions  20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
    Mounting  on 35 mm DIN mounting rail acc. to EN 60715:2001
    Data for application in connection
    with Ex-areas
    EC-Type Examination Certificate  PTB 00 ATEX 2080 , for additional certificates see www.pepperl-fuchs.com
    Group, category, type of protection  ¬ II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC
    Input  [Ex ia] IIC, [Ex ia] IIIC
    Voltage U
    o
     10.5 V
    Current I
    o
      13 mA
    Power P
    o
      34 mW (linear characteristic)
    Supply  
    Maximum safe voltage  U
    m
    253 V AC / 125 V DC (Attention! U
    m
     is no rated voltage.)
    Output  
    Contact loading  253 V AC/2 A/cos  φ  > 0.7; 126.5 V AC/4 A/cos  φ > 0.7; 40 V DC/2 A resistive load
    Maximum safe voltage  U
    m
    253 V AC (Attention! The rated voltage can be lower.)
    Statement of conbity  Pepperl+Fuchs
    Group, category, type of protection  ¬ II (3)G [Ex ic] IIC; [Ex nL] IIC
    Input  [Ex ic] IIC; [Ex nL] IIC
    Voltage U
    o
    10.5 V
    Current I
    o
    13 mA
    Power P
    o
    34 mW (linear characteristic)
    Release date  2012-07-06 08:53 Date of issue  2012-07-17 132960_eng.xml
    Technical data KFD2-SR2-Ex2.W
    Subject to reasonable modifications due to technical advances.  Copyright Pepperl+Fuchs, Printed in Germany
    Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 3
    Output 
    Contact loading  253 V AC/2 A/cos φ  > 0.7; 126.5 V AC/4 A/cos  φ > 0.7; 40 V DC/2 A resistive load
    Statement of conbity  TÜV 99 ATEX 1493 X , observe statement of conbity
    Group, category, type of protection,
    temperature class
    ¬ II 3G Ex nA nC IIC T4
    Output 
    Contact loading  50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
    Electrical isolation  
    Input/Output  safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
    Input/power supply  safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
    Directive conbity  
    Directive 94/9/EC  EN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2005 , EN 61241-11:2006
    International approvals
    FM  approval  
    Control drawing  116-0035
    CSA approval  
    Control drawing  116-0047
    IECEx approval  IECEx PTB 11.0034
    Approved for  [Ex ia] IIC , [Ex ia] IIIC , [Ex ia] I
    General inbation
    Supplementary inbation  EC-Type Examination Certificate, Statement of Conf ormity, Declaration of Conbity, Attestation of
    Conbity and instructions have to be observed where applicable. For inbation see www.pepperl-fuchs.com.
    Release date  2012-07-06 08:53 Date of issue  2012-07-17 132960_eng.xml
    Technical data KFD2-SR2-Ex2.W
    Subject to reasonable modifications due to technical advances.  Copyright Pepperl+Fuchs, Printed in Germany
    Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 4
    Power feed module KFD2-EB2
    The power feed module is used to supply  the devices with 24 V DC via the Power Ra il. The fuse-protected power feed module
    can supply up to 150 individual devices depending on the power co nsumption of the devices. A galvanically isolated mechanical
    contact uses the Power Rail to transmit collective error messages.
    Power Rail UPR-03
    The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an  aluminium profile rail 35 mm x 15 mm. To make
    electrical contact, the de vices are simply engaged.
    Profile Rail K-DUCT with Power Rail
    The profile rail K-DUCT is an aluminum profile rail with Power Ra il insert and two integral cable ducts for system and field cab les.
    Due to this assembly no additional cable guides are necessary.
    Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
    Configuration
    789
    10 11 12
    123
    456
    13 14 15
    1
    2
    PWR CHK OUT
    S1
    S2
    S3
    123
    123
    S1
    S3
    II
    S2
    I
    Switch b
    Operating status
    Factory settings: switch 1, 2 and 3 in b I
    S Function Position
    1 Mode of operation
    Output I (relay)
    energized
    with high b current I
    with low b current II
    2 Mode of operation
    Output II (relay)
    energized
    with high b current I
    with low b current II
    3 Line fault detection ON I
    OFF II
    Control circuit Input signal
    Initiator high impedance/
    contact opened
    low b current
    Initiator low impedance/
    contact closed
    high b current
    Lead breakage,
    lead short-circuit
    Line fault
    Accessories
在線詢盤/留言
  • 免責聲明:以上所展示的信息由企業(yè)自行提供,內(nèi)容的真實性、準確性和合法性由發(fā)布企業(yè)負責,本網(wǎng)對此不承擔任何保證責任。我們原則 上建議您選擇本網(wǎng)高級會員或VIP會員。
    企業(yè)信息
    上海工午電氣有限公司
    會員級別:試用會員
    ------------ 聯(lián)系方式 ------------
    聯(lián)系人:楊文遠(先生)
    聯(lián)系電話:021-50931161
    聯(lián)系手機:13917524517
    傳真號碼:021-50931161
    企業(yè)郵箱:yangwenyuan0202@163.com
    網(wǎng)址:
    郵編:200136
    推薦供應
    0571-87774297