適用于具有中等要求的應(yīng)用的 CPU,用于 S7-1500 控制器產(chǎn)品系列中的程序/數(shù)據(jù)存儲
-
具有高處理速度,適用于二進(jìn)制和浮點(diǎn)運(yùn)算
-
在具有集中式和分布式 I/O 的生產(chǎn)線上作為集中式控制器使用
-
PROFINET IO IRT 接口,帶 2 端口交換機(jī)
-
PROFINET I/O 控制器,用于在 PROFINET 上運(yùn)行分布式 I/O
-
用于連接 CPU 作為 SIMATIC 或 非西門子 PROFINET I/O 控制器下的 PROFINET 設(shè)備的 PRIFINET 智能設(shè)備
-
等時(shí)同步模式
-
集成運(yùn)動(dòng)控制功能,可以控制速度控制軸和定位軸,支持外部編碼器
-
集成 Web 服務(wù)器,帶有創(chuàng)建用戶定義的 Web 站點(diǎn)的選項(xiàng)
-
運(yùn)行 CPU 所需的 SIMATIC 存儲卡
Area of application
The CPU 1513-1 PN is the CPU with a medium program and data memory for applications that also contain distributed automation structures alongside central I/O. It can be used as a PROFINET IO controller or as distributed inbligence (PROFINET I-Device). The integrated PROFINET IO IRT interface is designed as 2-port switch so that a linear topology can be set up in the system. In addition, the CPU offers comprehensive control functionalities as well as the ability to connect drives via standardized PLC-open blocks.
Design
The CPU 1513-1 PN has:
-
A powerful processor:
The CPU achieves command execution times as low as 40 ns per binary instruction.
-
A large work memory:
300 KB for program, 1.5 MB for data
-
SIMATIC memory cards as load memory;
permit additional functions such as datalog and archives
-
Flexible expansion capability:
single-tier configuration with max. 32 modules (CPU + 31 modules)
-
Display with functions for the
-
Display of overview inbation such as IP address of the integrated interface, station name, higher level designation, b designation, etc.,
-
Display of diagnostic inbation
-
Display of module inbation
-
Display of display settings
-
Display of a user-definable logo
-
Setting of IP addresses
-
Setting of date and time
-
Selection of the operating mode
-
Resetting of the CPU to factory settings
-
Disabling/enabling of the display
-
Enabling of protection levels
-
PROFINET IO IRT interface for connecting distributed I/O via PROFINET
Functions
-
Perbance
-
Faster command processing, depending on the CPU type, language extensions and new data types
-
Even shorter response times of the CPUs due to considerably faster backplane bus
-
Powerful network connection:
each CPU is equipped with PROFINET IO IRT (2-port switch) as standard interface.
-
Integrated technology
-
Connection of analog and PROFIdrive-capable drives via standardized blocks (PLCopen)
-
Support of speed-controlled and bing axes as well as external encoders, bally precise gearing between axes
-
Trace functions for all CPU tags, both for diagnostics in real time as well as for sporadic error detection
-
Comprehensive control functionalities, e.g. easily configurable blocks for automatic optimization of the control beters for optimum control quality
-
Security Integrated
-
Password-based know-how protection against unauthorized reading and modification of program blocks
-
Copy protection for tying individual blocks to the serial number of the SIMATIC memory card: The block can only run if the configured memory card is inserted into the CPU.
-
4-level authorization concept:
Communication to the HMI devices can also be restricted.
-
Manipulation protection:
The controller recognizes changed or unauthorized transmissions of the engineering data.
-
Design and handling
-
Display for displaying overview inbation:
e.g. station name, higher level designation, b designation, etc., diagnostic inbation, module inbation, display settings.
-
Possible operations on the display:
set addresses of the CPU or connected Ethernet communications processors, set date and time, select operating mode of CPU, reset CPU to factory settings, disable/enable display, activate protection levels.
-
Integrated system diagnostics
-
System diagnostics inbation is displayed consistently and in plain text in the display, TIA Portal, HMI devices and web server, even for messages from the drives, and updated even if the CPU is in STOP mode.
-
Integrated in the firmware of the CPU, no special configuration is required
-
SIMATIC memory card (required for operation of the CPU)
-
Used as plug-in load memory or for updating the firmware.
-
Additionally for storing additional documents or csv files (for recipes and archives)
-
Creation of data blocks for storage/reading of data via SFCs of the user program
-
Datalog (archives) and recipes
-
Storage of csv files for recipes and archives on the SIMATIC memory card;
easy access to plant-relevant operating data using Office tools or via a web server
-
Easy access to configuration data of the machine by means of a web browser or SD card reader (two-way data exchange from and to the controller)
-
Programming
-
Programming with STEP 7 Professional, V12 and higher
-
Migration tool for migrating from SIMATIC S7-300/S7-400 to S7-1500, converts the program code largely automatically. Non-convertible code is logged and can be manually adapted.
-
STEP 7 V11 projects can continue to be used with STEP 7 V12 in compatibility mode.
-
S7-1200 basic programs can be transferred to the S7-1500 by means of copy&paste.
Technical Specifications
Order number
|
6ES7513-1AL00-0AB0
|
|
CPU 1513-1 PN, 300KB PROG., 1,5MB DATA
|
Product type designation
|
|
General inbation
|
|
Engineering with
|
|
|
V13 SP1
|
Display
|
|
Screen diagonal (cm)
|
3.45 cm
|
Supply voltage
|
|
Type of supply voltage
|
24 V DC
|
Power losses
|
|
Power loss, typ.
|
5.7 W
|
Memory
|
|
Work memory
|
|
|
300 kbyte
|
|
1.5 Mbyte
|
Load memory
|
|
|
32 Gbyte
|
CPU processing times
|
|
for bit operations, typ.
|
40 ns
|
for word operations, typ.
|
48 ns
|
for fixed point arithmetic, typ.
|
64 ns
|
for floating point arithmetic, typ.
|
256 ns
|
Counters, timers and their retentivity
|
|
S7 counter
|
|
|
2 048
|
IEC counter
|
|
|
Any (only limited by the main memory)
|
S7 times
|
|
|
2 048
|
IEC timer
|
|
|
Any (only limited by the main memory)
|
Data areas and their retentivity
|
|
Flag
|
|
|
16 kbyte
|
Address area
|
|
I/O address area
|
|
|
32 kbyte; All bs are in the process image
|
|
32 kbyte; All outputs are in the process image
|
Time of day
|
|
Clock
|
|
|
Hardware clock
|
Interfaces
|
|
1st interface
|
|
Interface types
|
|
|
2
|
|
Yes
|
|
Yes; X1
|
Protocols
|
|
|
Yes
|
|
Yes
|
|
Yes
|
|
Yes
|
|
Yes
|
|
Yes
|
Protocols
|
|
Number of connections
|
|
|
128; via integrated interfaces of the CPU and connected CPs / CMs
|
PROFINET IO Controller
|
|
Services
|
|
|
128; In total, up to 256 distributed I/O devices can be connected via PROFIBUS or PROFINET
|
|
64
|
|
128
|
Isochronous mode
|
|
Isochronous operation (application synchronized up to terminal)
|
Yes; With minimum OB 6x cycle of 500 µs
|
supported technology bs
|
|
Motion
|
Yes
|
|
|
|
6; Requirement: There must be no other motion technology bs created
|
|
|
|
6; Requirement: There must be no other motion technology bs created
|
|
|
|
3; Requirement: There must be no other motion technology bs created
|
|
|
|
6; Requirement: There must be no other motion technology bs created
|
Controller
|
|
|
Yes; Universal PID controller with integrated optimization
|
|
Yes; PID controller with integrated optimization for valves
|
|
Yes; PID controller with integrated optimization for temperature
|
Counting and measuring
|
|
|
Yes
|
Ambient conditions
|
|
Ambient temperature in operation
|
|
|
0 °C
|
|
60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the display is switched off
|
|
0 °C
|
|
40 °C; Display: 40 °C, at an operating temperature of typically 40 °C, the display is switched off
|
Configuration
|
|
programming
|
|
Programming language
|
|
|
Yes
|
|
Yes
|
|
Yes
|
|
Yes
|
|
Yes
|
Know-how protection
|
|
|
Yes
|
|
Yes
|
|
Yes
|
Access protection
|
|
|
Yes
|
|
Yes
|
|
Yes
|
|
Yes
|
Dimensions
|
|
Width
|
35 mm
|
Height
|
147 mm
|
Depth
|
129 mm
|
Weights
|
|
Weight, approx.
|
430 g
|
More inbation
Further inbation and downloads