Emerson Liebert® GXT3-10000RT230
Liebert® GXT3-10000RT230 Features :
Design Requirements : | |
---|---|
Model Rating |
9000W/10000VA |
Output Load Capacity |
220 / 230 / 240 |
Internal Battery |
Valve-regulated, non-spillable, lead acid cells. |
Battery Reserve Time |
Minimum 3 minutes with an ambient temperature of 25°C (77°F). |
Battery Recharge |
The UPS shall contain a battery charger designed to prolong battery life. Recharge time for UPS internal batteries shall be 3 hours maximum to 90% capacity after a complete discharge into full load. |
Frequency |
The UPS shall auto-sense mains frequency of 50Hz or 60Hz when first powered up and shall use this frequency as the default output frequency. |
Mains Power Factor |
>0.99 lagging at rated load. |
Mains Output, UPS Inverters : | |
Voltage Configuration |
50Hz, single-phase, 2-wire-plus-ground. |
Voltage Regulation |
L-N: ±3% steady state. |
Frequency Regulation |
±3.5Hz synchronized to mains. |
Frequency Slew Rate |
1.0Hz per second maximum |
Load Power Factor Range |
0.65 lagging to 1.0 (unity) |
Voltage Distortion |
Sinusoidal Waveb; ≤3% total harmonic distortion (THD) into a 100% linear load; ≤5% THD into a 100% non-linear load with a crest factor ratio of 3:1. |
Voltage Transient Response |
±7% on-line or Battery mode for 0-100-0 % loading of the UPS, ±4% on-line or Battery mode for 20-100-20 % loading of the UPS. |
Transient Recovery Time |
To nominal voltage within 166 milliseconds. |
Efficiency |
92% AC-AC |
Accessories : | |
RMKIT 18 32 |
Rackmount Kit for GXT3 |
Emerson Liebert® GXT3-10000RT230