Rating Low High Number GO-135S Sensor Number GO-135S Number GO-135S Number GO-135S Range
15 43 182 SRPE30A15 緯軒機電106.00
20 58 254 SRPE30A20 緯軒機電106.00 30 SEDA24AT0030 緯軒機電214.00 SEHA24AT0030 緯軒機電530.00 25 73 332 SRPE30A25 緯軒機電106.00
30 87 415 SRPE30A30 緯軒機電106.00
40 118 501 SRPE60A40 緯軒機電106.00
50 148 637 SRPE60A50 緯軒機電106.00 60 SEDA24AT0060 緯軒機電214.00 SEHA24AT0060 緯軒機電530.00 12-3/0 Cu 60 178 777 SRPE60A60 緯軒機電106.00 TCAL18 緯軒機電3.00 12-3/0 Al 70 206 863 SRPE100A70 緯軒機電106.00
80 236 999 SRPE100A80 緯軒機電106.00 100 SEDA24AT0100 緯軒機電312.00 SEHA24AT0100 緯軒機電634.00 90 267 1138 SRPE100A90 緯軒機電106.00
100 297 1280 SRPE100A100 緯軒機電106.00
110 328 1426 SRPE150A110 緯軒機電106.00
125 374 1640 SRPE150A125 緯軒機電106.00 150 SEDA24AT0150 緯軒機電837.00 SEHA24AT0150 緯軒機電1427.00
150 450 1991 SRPE150A150 緯軒機電106.00
SE150 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SEL, SEP2; 2-Pole, UL/CSA: 150A, 480 Vac Max., IEC 947-2: 160A, 415 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
UL 489 IC @480 Vac UL 489 IC @480 Vac
Adj. Inst. 65kA 100kA
Ampere Trip Range Amps Product List Price Current Product List Price Product List Price Product List Price Wire
Rating Low High Number GO-135S Sensor Number GO-135S Number GO-135S Number GO-135S Range
15 43 182 SRPE30A15 緯軒機電106.00
20 58 254 SRPE30A20 緯軒機電106.00 30 SELA24AT0030 緯軒機電549.00 SEPA24AT0030 緯軒機電895.00 25 73 332 SRPE30A25 緯軒機電106.00
30 87 415 SRPE30A30 緯軒機電106.00
40 118 501 SRPE60A40 緯軒機電106.00
50 148 637 SRPE60A50 緯軒機電106.00 60 SELA24AT0060 緯軒機電549.00 SEPA24AT0060 緯軒機電895.00 12-3/0 Cu 60 178 777 SRPE60A60 緯軒機電106.00 TCAL18 緯軒機電3.00
70 206 863 SRPE100A70 緯軒機電106.00 12-3/0 Al
80 236 999 SRPE100A80 緯軒機電106.00 100 SELA24AT0100 緯軒機電744.00 SEPA24AT0100 緯軒機電1179.00 90 267 1138 SRPE100A90 緯軒機電106.00
100 297 1280 SRPE100A100 緯軒機電106.00
110 328 1426 SRPE150A110 緯軒機電106.00
125 374 1640 SRPE150A125 緯軒機電106.00 150 SELA24AT0150 緯軒機電1808.00 SEPA24AT0150 緯軒機電2777.00
150 450 1991 SRPE150A150 緯軒機電106.00
2SEL, SEP UL current limiting.
Note: All Spectra? breakers UL listed as HACR type.
All Spectra? breakers marked CE.
Product Number Structure
S E D A 2 4 A T 0030
Frame Rating Interruption Continuous Voltage Trip Trip Sensor
Family (Amperes) Rating (480V) Load Rating Poles Rating Unit Function (Max Amps)
S = Spectra? E = 150 D = 18 kA A = Standard 2 = 2 poles 4 = 480V A = RMS1 T = LSI1 0030
H = 25 kA 3 = 3 poles 6 = 600V 0060
L = 65 kA 0100
P = 100 kA 0150
1Adjustable Instantaneous with Tracking Short Time (Long Time established via Interchangeable Rating Plugs).
Note: This inbation is provided for interpreting product numbers (it should not be used to build product numbers).
Molded Case Circuit Breakers
Industrial Circuit Breaker Accessories
15-150A Circuit Breakers, Electronic Trip, Spectra? RMS, SE150 Line Circuit Breakers
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-9
to change without notice
SG600 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SGD, SGH; UL/CSA: 400A, 600 Vac Max., IEC 947-2: 400A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 65kA (240 Vac) 35kA
Ampere Trip Ampere Range Product List Price Current Product List Price Product List Price Product List Price Wire
Rating Low High Number GO-135S Sensor Poles Number GO-135S Number GO-135S Number GO-135S Range
125 380 1275 SRPG400A125 緯軒機電106.00 2-pole lug kit 150 455 1530 SRPG400A150 緯軒機電106.00 (2) 2/0-500 Cu
175 530 1785 SRPG400A175 緯軒機電106.00 2 SGDA22AT04004 緯軒機電1540.00 SGHA26AT0400 緯軒機電1959.00 TCLK2655 緯軒機電28.00 or
200 605 2040 SRPG400A200 緯軒機電106.00 (1) 8-600 Cu
225 680 2295 SRPG400A225 緯軒機電106.00 400
250 755 2550 SRPG400A250 緯軒機電106.00 3-pole lug kit 300 905 3060 SRPG400A300 緯軒機電106.00 3 SGDA32AT04004 緯軒機電1860.00 SGHA36AT0400 緯軒機電2383.00 (2) 2/0-500 Al
350 1060 3570 SRPG400A350 緯軒機電106.00 TCLK3655 緯軒機電42.00 or
400 1210 4080 SRPG400A400 緯軒機電106.00 (1) 8-600 Al
4Rated 240 Vac max.
5Order one kit for either line or load end; two kits required for both.
Note: All Spectra? breakers UL listed as HACR type. All Spectra? breakers marked CE.
125-600A Circuit Breakers, Electronic Trip, Spectra? RMS, SG600 Digital, Solid-State Spectra? RMS Breakers
70-250A Circuit Breakers, Electronic Trip, Spectra? RMS, SF250 Line Circuit Breakers
SF250 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350
SFH; 2-Pole, UL/CSA: 250A, 480 Vac Max., IEC 947-2: 250A, 415 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable Instantaneous
UL 489 IC @480 Vac
Trip Ampere Range
35kA
Ampere Product List Price Current Product List Price Product List Price Wire
Rating Low Hi gh Number GO-135S Sensor Number GO-135S Number GO-135S Range
70 205 700 SRPF250A70 緯軒機電106.00
90 265 900 SRPF250A90 緯軒機電106.00
100 295 1000 SRPF250A100 緯軒機電106.00
110 325 1100 SRPF250A110 緯軒機電106.00 8-350 Cu 125 370 1250 SRPF250A125 緯軒機電106.00 250 SFHA24AT0250 緯軒機電1134.00 TCAL29 緯軒機電8.00 150 440 1500 SRPF250A150 緯軒機電106.00 8-350 Al
175 515 1750 SRPF250A175 緯軒機電106.00
200 590 2000 SRPF250A200 緯軒機電106.00
225 665 2250 SRPF250A225 緯軒機電106.00
250 736 2500 SRPF250A250 緯軒機電106.00
Molded Case Circuit Breakers
Industrial Circuit Breaker Accessories
Product Number Structure
1Adjustable Instantaneous with Tracking Short Time (Long Time established via Interchangeable Rating Plugs).
Note: This inbation is provided for interpreting product numbers (it should not be used to build product numbers).
S F H A 2 4 A T 0250
Frame Rating Interruption Continuous Voltage Trip Trip Sensor
Family (Amperes) Rating (480V) Load Rating Poles Rating Unit Function (Max Amps)
S = Spectra? F = 250 H = 35 kA A = Standard 2 = 2 poles 4 = 480V A = RMS1 T = LSI1 0250
L = 65 kA 3 = 3 poles 6 = 600V
P = 100 kA
Product Number Structure
S G D A 2 2 A T 0400
Frame Rating Interruption Continuous Voltage Trip Trip Sensor
Family (Amperes) Rating (480V) Load Rating Poles Rating Unit Function (Max Amps)
S = Spectra? G = 600 D = 65 kA2 A = Standard 2 = 2 poles 2 = 240V A = RMS1 T = LSI3 0400
H = 35 kA H = 100% 3 = 3 poles 6 = 600V 0600
L = 65 kA L = 100%
P = 100 kA P = 100% 2 SGD rated 65kA at 240V.
3Adjustable Instantaneous with Tracking Short Time (Long Time established via Interchangeable Rating Plugs).
Note: This inbation is provided for interpreting product numbers (it should not be used to build product numbers).
Components: Parts
1
1-10 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, UL/CSA: 800A, 600 Vac Max., IEC 947-2:800A 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 50kA 65kA
Ampere Trip Ampere Range Product List Price Current Product List Price Product List Price Product List Price Wire
Rating Low High Number GO-135S Sensor Poles Number GO-135S Number GO-135S Number GO-135S Range
300 940 3015 SRPK800A300 緯軒機電106.00
400 1255 4015 SRPK800A400 緯軒機電106.00 2 SKHA26AT0800 緯軒機電3377.00 SKLA26AT0800 緯軒機電4301.00 (3) 3/0-500 Cu
500 1570 5020 SRPK800A500 緯軒機電106.00 800 TCAL81 緯軒機電47.00 600 1875 6195 SRPK800A600 緯軒機電106.00
700 2155 7420 SRPK800A700 緯軒機電106.00 3 SKHA36AT0800 緯軒機電4323.00 SKLA36AT0800 緯軒機電5234.00 (3) 3/0-500 Al 800 2440 8705 SRPK800A800 緯軒機電106.00
SK1200 Line, Suitable for Reverse Feed, UL File E-11592, CSA LR 40350, UL/CSA: 1200A, 600 Vac Max., IEC 947-2: 1250A, 690 Vac Max.
Rating Plug Frame Terminal Lugs for Front Connection (Cu/Al)
Adjustable
UL 489 IC @480 Vac UL 489 IC @480 Vac
Instantaneous 50kA 65kA
Ampere Trip Ampere Range Product List Price Current Product List Price Product List Price Product List Price Wire
Rating Low High Number GO-135S Sensor Poles Number GO-135S Number GO-135S Number GO-135S Range
600 1825 6110 SRPK1200A600 緯軒機電106.00
700 2125 7125 SRPK1200A700 緯軒機電106.00 2 SKHA26AT1200 緯軒機電7057.00 SKLA26AT1200 緯軒機電7958.00 (4) 250-500 Cu
800 2430 8145 SRPK1200A800 緯軒機電106.00 1200 TCAL125 緯軒機電76.00 900 2735 9160 SRPK1200A900 緯軒機電106.00
1000 3040 10180 SRPK1200A1000 緯軒機電106.00 3 SKHA36AT1200 緯軒機電7679.00 SKLA36AT1200 緯軒機電8586.00 (4) 250-500 Al 1200 3650 12215 SRPK1200A1200 緯軒機電106.00
Note: All Spectra? breakers UL listed as HACR type.
All Spectra? breakers marked CE.
Molded Case Circuit Breakers
Industrial Circuit Breaker Accessories
Product Number Structure
1Adjustable Instantaneous with Tracking Short Time (Long Time established via Interchangeable Rating Plugs).
Note: This inbation is provided for interpreting product numbers (it should not be used to build product numbers).
S K H A 2 6 A T 0800
Frame Rating Interruption Continuous Voltage Trip Trip Sensor
Family (Amperes) Rating (480V) Load Rating Poles Rating Unit Function (Max Amps)
S = Spectra? K = 1200 H = 50 kA A = Standard 2 = 2 poles 6 = 600V A = RMS1 T = LSI1 0800
L = 65 kA H = 100% 3 = 3 poles 1200
P = 100 kA L = 100%
P = 100%
300-1200A Circuit Breakers, Electronic Trip, Spectra? RMS
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-11
to change without notice
MicroVersaTrip? Plus and PM Rating Plug Selection —
All Plugs List Price 緯軒機電106.00, GO-135S
Circuit Breaker Sensor Rating Plug Rating Plug
Frame Rating Rating (Amperes) Product No.
150 60 SRPG150B60
80 SRPG150B80
100 SRPG150B100
125 SRPG150B125
150 SRPG150B150
400 150 SRPG400B150
200 SRPG400B200
SGHB, SGHH, SGLB, 225 SRPG400B225
SGLL, SGPB, SGPP 250 SRPG400B250
300 SRPG400B300
350 SRPG400B350
400 SRPG400B400
600 300 SRPG600B300
400 SRPG600B400
450 SRPG600B450
500 SRPG600B500
600 SRPG600B600
1MicroVersaTrip? PM Trip Units require 24 Vdc control power and voltage sensing signals. Refer to pages 1-12 to 1-14.
Note: All Spectra? breakers UL listed as HACR type.
All Spectra? breakers marked CE.
Microversatrip? Plus and PM Rating Plug Selection —
All Plugs List Price 緯軒機電106.00, GO-135S
Circuit Breaker Sensor Rating Plug Rating Plug
Frame Rating Rating (Amperes) Product No.
300 SRPK800B300
400 SRPK800B400
800 500 SRPK800B500
600 SRPK800B600
SKHB, SKHH, SKLB, 700 SRPK800B700
SKLL, SKPB, SKPP 800 SRPK800B800
600 SRPK1200B600
700 SRPK1200B700
1200 800 SRPK1200B800
1000 SRPK1200B1000
1200 SRPK1200B12002
1Microversatrip? PM Trip Units require 24 Vdc control power and voltage sensing signals. Refer to pages 1-12 to 1-14.
2Not suitable for use with 100% rated, 1000A breaker frame.
Note: All Spectra? breakers UL listed as HACR type.
All Spectra? breakers marked CE.
300-1200A Circuit Breakers, Electronic Trip, Spectra? RMS, SK1200 with MicroVersaTrip? Plus and PM1
60-600A Circuit Breakers, Electronic Trip, Spectra? RMS , with MicroVersaTrip? PM Trip Unit1
Molded Case Circuit Breakers
Industrial Circuit Breaker Accessories
Rating Plugs
Components: Parts
1
1-12 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Molded Case Circuit Breakers
Power Management System Accessories
Spectra? RMS Circuit Breakers with MicroVersaTrip? Plus and MicroVersaTrip? PM Trip Units
All Devices UL Listed for Factory or Field Installation (UL File No. E-57253)
Required Accessories
Type Accessories
Standard –
Ground Fault Option with 3-phase, 4-wire Neutral Current Sensor and Terminal Block
MicroVersaTrip? Plus Trip Unit or 1-phase, 3-wire service or Neutral Current Sensor and Junction Box
Control Power Option Power Supply Plate or Voltage Module1 or Power Supply Assembly2
Power Supply Plate and Voltage Conditioner Plate or Voltage Module1
Standard or with Protective Relaying or Power Supply Assembly2 and Voltage Conditioner Assembly2
MicroVersaTrip? PM Trip Unit Junction Box, Cable Harness and Auxiliary Switch
Ground Fault Option with 3-phase, 4-wire Neutral Current Sensor
or 1-phase, 3-wire service
1For installation into GE Spectra? Series Switchboards only.
2Requires fuse protection and other components; refer to accessory detail for additional inbation.
?Power Supply Plate
The Power Supply Plate is used to provide +24 Vdc control power to Spectra? RMS Molded
Case Circuit Breakers with MicroVersaTrip? PM or MicroVersaTrip? Plus trip systems via the
Distribution Cable System. The Power Supply Plate includes the Power Supply Assembly
(product number SPSAA) as an integral component and also includes fuse protection for AC
source b. Supplemental +24 Vdc b terminals are provided for backup control power
applications. Five versions are available. Not suitable for 400 Hz. List Price
Debion Voltage Rating Product Number GO-135PM
The Power Supply Plate is rated 24 watts 120 Vac SPSA120 緯軒機電1215.00
(+24 Vdc at 1.0 amperes) and has the maximum 208 Vac SPSA208 緯軒機電1215.00
capacity to power a distribution Cable System 240 Vac SPSA240 緯軒機電1215.00
consisting of 20 breakers and has a maximum 480 Vac SPSA480 緯軒機電1215.00
system cable length of 40 feet. 600 Vac SPSA600 緯軒機電1215.00
Voltage Conditoner Plate
The Voltage Conditioner Plate is used to provide voltage sensing signals to Spectra?
RMS Molded Case Circuit Breakers with MicroVersaTrip? PM Trip Units via the Distribution
Cable System. The Voltage Conditioner Plate includes the Voltage Conditioner Assembly
(product number SVCAA) as an integral component and also includes fuse protection
for the AC source b terminals and three 1-VA high accuracy potential transbers.
The Voltage Conditioner Plate requires a control power source of +24 Vdc to operate properly
(the Power Supply Assembly or Power Supply Plate can provide this required b). The unit
also requires AC direct voltage bs from the AC source. A GE POWER LEADER? network
(commnet) connection is provided. Seven versions are available. Not suitable for 400 Hz. List Price
Voltage Rating and Service Type Comments Product Number GO-135PM
120 Vac Wye system Phase to Neutral potential SVCA120Y 緯軒機電1000.00
208 Vac Wye system Phase to Phase potential SVCA208Y 緯軒機電1000.00
240 Vac Delta system Phase to Phase potential SVCA240D 緯軒機電1000.00
277 Vac Wye system Phase to Neutral potential SVCA277Y 緯軒機電1000.00
480 Vac Wye system Phase to Phase potential SVCA480Y 緯軒機電1000.00
480 Vac Delta system Phase to Phase potential SVCA480D 緯軒機電1000.00
600 Vac Delta system Phase to Phase potential SVCA600D 緯軒機電1000.00
Note: The Voltage Conditoner Plate has the maximum capacity to power a Distribution Cable System consisting of
20 breakers and has a maximum system cable length of 40 feet.
Distribution Cable Junction Box
The Distribution Cable Junction Box is a modular connector used to provide quick, easy and
reliable attachment of Spectra? RMS Molded Case Circuit Breakers with MicroVersaTrip? Plus
trip systems or MicroVersaTrip? PM trip systems to the Distribution Cable System. The Junction
Box contains two Distribution Cable Harness plugs, one breaker plug and a terminal block for
the connection of a neutral current sensor and an auxiliary switch. Product number SDCJBA
is for general purpose OEM applications. Product number SDCJBB is designed for mounting
in Spectra? Series Panelboards. List Price
Debion Product Number GO-135PM
Distribution Cable Junction Box SDCJBA3 緯軒機電155.00
Distribution Cable Junction Box SDCJBB 緯軒機電155.00
3Limited availability—obselete when inventory depleted.
Power Supply Plate
Voltage Conditioner Plate
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-13
to change without notice
Molded Case Circuit Breakers
Power Management System Accessories
Spectra? RMS Circuit Breakers with MicroVersaTrip? Plus and MicroVersaTrip? PM Trip Units
All Devices UL Listed for Factory or Field Installation (UL File No. E-57253)
Distribution Cable Harness3
The Distribution Cable Harness is a modular connector used to carry electronic signals
and/or control power between Spectra? RMS Molded Case Circuit Breakers with
MicroVersaTrip? Plus or MicroVersaTrip? PM Trip Units and Distribution Cable accessories.
The harnesses come in three lengths. List Price
Debion Harness Length Product Number GO-135PM
Distribution Cable Harness 11 inches SDCHA11 緯軒機電70.00
Distribution Cable Harness 30 inches SDCHA30 緯軒機電80.00
Distribution Cable Harness 60 inches SDCHA60 緯軒機電100.00
3Cannot be connected together. Use 30 inch Distribution Cable Extension (SDCEA30) to extend.
Distribution Cable Extension
The Distribution Cable Extension is used to provide modular expansion of the Distribution
Cable System. List Price
Debion Harness Length Product Number GO-135PM
Distribution Cable Extension 30 inches SDCEA30 緯軒機電80.00
Distribution Cable Terminal Block
The Distribution Cable Terminal Block is a modular attachment primarily used to provide
an alternate means of b to Spectra? RMS Molded Case Circuit Breakers with
MicroVersaTrip? Plus or MicroVersaTrip? PM Trip Units. The Terminal Block plugs into the
breaker distribution cable receptacle allowing the direct connection of breaker signals
via screw terminals. This allows point-to-point wiring of breakers instead of using the
Distribution Cable System. List Price
Debion Product Number GO-135PM
Distribution Cable Terminal Block SDCTBA11 緯軒機電110.00
Power Supply Assembly
The Power Supply Assembly is used to provide +24 Vdc Control Power to Spectra? RMS
Molded Case Circuit Breakers with MicroVersaTrip? Plus or MicroVersaTrip? PM trip systems
via the Distribution Cable System. The assembly requires a minimum b voltage of 85
Vac to operate properly (the maximum voltage rating is 240 Vac). Supplemental +24 Vdc
b terminals are provided for backup control power applications. The b must be
fused with 1/2 ampere class CC fuses (not included). Not suitable for 400 Hz. List Price
Debion Voltage Rating Product Number GO-135PM
The Power Supply Assembly is rated 24 watts 85 - 240 Vac SPSAA 緯軒機電1000.00
(+24 Vdc @ 1.0 ampere) and has the maximum
capacity to power a Distribution Cable System
consisting of 20 breakers and has a maximum
system cable length of 40 feet.
Distribution Cable Extension
Distribution Cable Terminal Block
Power Supply Assembly
Required Accessories
Type Accessories
Standard –
Ground Fault Option with 3-phase, 4-wire Neutral Current Sensor and Terminal Block
MicroVersaTrip? Plus Trip Unit or 1-phase, 3-wire service or Neutral Current Sensor and Junction Box
Control Power Option Power Supply Plate or Voltage Module1 or Power Supply Assembly2
Power Supply Plate and Voltage Conditioner Plate or Voltage Module1
Standard or with Protective Relaying or Power Supply Assembly2 and Voltage Conditioner Assembly2
MicroVersaTrip? PM Trip Unit Junction Box, Cable Harness and Auxiliary Switch
Ground Fault Option with 3-phase, 4-wire Neutral Current Sensor
or 1-phase, 3-wire service
1For installation into GE Spectra? Series Switchboards only.
2Requires fuse protection and other components; refer to accessory detail for additional inbation.
Distribution Cable Harness
Components: Parts
1
1-14 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Molded Case Circuit Breakers
Power Management System Accessories
Spectra? RMS Circuit Breakers with MicroVersaTrip? Plus and MicroVersaTrip? PM Trip Units
All Devices UL Listed for Factory or Field Installation (UL File No. E-57253)
Voltage Modules
The Voltage Module is used primarily as a Spectra? Series Switchboard component
to provide +24 Vdc Control Power to Spectra? RMS Molded Case Circuit Breakers with
MicroVersaTrip? Plus or MicroVersaTrip? PM Trip Units via the Distribution Cable System.
The Module also provides voltage sensing signals to Spectra? RMS Molded Case Circuit
Breakers with MicroVersaTrip? PM Trip Units on the same Distribution Cable System. The
Module contains both a Power Supply Plate and a Voltage Conditioner as integral components.
It also includes fuse protection for the AC source b terminals (the modules
pressure connectors which mate with the switchboard interior bus bars). A GE POWER
LEADER? Network (commnet) connection is provided as well as supplemental 24 Vdc
b terminals for backup control power applications. Seven versions are available. Not
suitable for 400 Hz.
List Price
Voltage Rating and Service Type Comments Product Number GO-135PM
120 Vac Wye system Phase to Neutral potential ADSVMA120Y 緯軒機電2350.00
208 Vac Wye system Phase to Phase potential ADSVMA208Y 緯軒機電2350.00
240 Vac Delta system Phase to Phase potential ADSVMA240D 緯軒機電2350.00
277 Vac Wye system Phase to Neutral potential ADSVMA277Y 緯軒機電2350.00
480 Vac Wye system Phase to Phase potential ADSVMA480Y 緯軒機電2350.00
480 Vac Delta system Phase to Phase potential ADSVMA480D 緯軒機電2350.00
600 Vac Delta system Phase to Phase potential ADSVMA600D 緯軒機電2350.00
Note: The Voltage Module has the maximum capacity to power a Distribution Cable System consisting of 20
breakers and has a maximum system cable length of 40 feet.
Voltage Module Exterior View Voltage Module Interior View
Voltage Conditioner Assembly
Voltage Conditioner Assembly
The Voltage Conditioner Assembly is used to provide voltage sensing signals to Spectra?
RMS Molded Case Circuit Breakers with MicroVersaTrip? PM Trip Units via the Distribution
Cable System. The Voltage Conditioner Assembly requires a control power source of +24
Vdc to operate properly (the Power Supply Assembly or Power Supply Plate can provide
this required b). The unit also requires 120 Vac voltage bs from the secondary
of three 1-VA high accuracy potential transbers (not included). The primary side of
the potential transbers must be fused with three, 1/2 ampere class CC fuses (not
included). A GE POWER LEADER? network (commnet) connection is provided. Not suitable
for 400 Hz.
List Price
Debion Voltage Rating Product Number GO-135PM
Requires 120 Vac voltage bs from the 120 Vac SVCAA 緯軒機電680.00
secondary of three 1.0 VA high accuracy
potential transbers
Note: the Voltage Conditioner Assembly has the maximum capacity to power a Distribution Cable System
consisting of 20 breakers and has a maximum system cable length of 40 feet.
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-15
to change without notice
Molded Case Circuit Breakers
Accessories–Other
Spectra? RMS Circuit Breakers with MicroVersaTrip? Plus and MicroVersaTrip? PM Trip Units
All Devices UL Listed for Factory or Field Installation Except Where Noted
Neutral Current Sensor
The neutral current sensor is used in conjunction with breakers that have a MicroVersaTrip?
Plus or MicroVersaTrip? PM Trip Unit with the optional ground fault function and the breaker
is connected to a grounded neutral service (3-phase, 4-wire or 1-phase, 3-wire). The neutral
current sensor provides an b signal to the breaker trip unit. Breakers connected to a
service without a neutral (3-phase, 3-wire) require no external connection or shorting of
the breaker cable connector for ground fault to function properly.
List Price
Breaker Type Sensor Rating (S) Product Number GO-135S
SG 150 TSRG201 緯軒機電532.00
SG 400 TSRG204 緯軒機電532.00
SG 600 TSRG206 緯軒機電532.00
SK 800 TSKG408 緯軒機電532.00
SK 1200 TSKG412 緯軒機電532.00
Voltage Current (mA) Product List Price
ac dc Inrush Cont Number GO-135S
120 125 500 6.0 SAST1 緯軒機電363.00
240 250 400 5.0 SAST2 緯軒機電363.00
— 12 1000 800 SAST51 緯軒機電363.00
24 24 300 10.0 SAST3 緯軒機電363.00
48 48 300 10.0 SAST4 緯軒機電363.00
1Not suitable for use with ground fault sensing and relaying equipment.
Note: UL listed at 200,000 AIC without internal accessories, 100,000 AIC with internally mounted accessories.
Auxiliary Switch
Auxiliary switches provide remote indication of whether the circuit breaker main
contacts are opened or closed via open or closed SPDT switch elements.
Switch Number of Auxiliary Switch List Price
Rating Switch Elements Product Number GO-135S
5A @240 Vac/ 1 b C SAUXPAB1 緯軒機電149.00
0.5A @ 125 Vdc 2 b C SAUXPAB2 緯軒機電295.00
Gold-Plated Contacts 1 b C SAUXGAB1 緯軒機電149.00
0.5A @ 30V 2 b C SAUXGAB2 緯軒機電295.00
One each 2 b C SAUXGPAB2 緯軒機電295.00
of above types
Shunt Trip
For remote tripping of breaker, use with momentary close contact. Not recommended for
use with latching relay contact since electronics in shunt trip will pulse power to the coil
if continuously energized, and breaker shunt tripping upon reclosure will be delayed 1-2
seconds at rated control voltage. (A short-circuit trip would be instantaneous.)
If maintained (latching relay) contact must be used and delayed shunt tripping is not
acceptable, use small bell alarm in series with control power for SE150 and SF250 frames
and auxiliary switch for SG600 and SK1200 breakers.
These devices are suitable for use with ground fault sensing and relaying equipment.
Maximum VA is 75. AC devices are UL listed for 50-60 Hz.
Red
White
Brown/white
Black
Black
All accessory contacts shown
with the circuit breaker in
tripped b.
All accessory contacts shown
with the circuit breaker in
tripped b.
Auxiliary Switch
Shunt Trip
Internal Accessories, Spectra? RMS Circuit Breakers
Components: Parts
1
1-16 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Actuator
All Spectra? circuit breakers are supplied with an actuator installed in the left-side pouch.
The actuator is removed when installing either a shunt trip or undervoltage release.
List Price
Debion Product Number GO-148C
Replacement Actuator SACTUATOR 緯軒機電250.00
Voltage Peak Current Product List Price
ac dc (mA) Number GO-135S
120 125 200 SAUV1 緯軒機電363.00
240 250 200 SAUV2 緯軒機電363.00
24 24 100 SAUV3 緯軒機電363.00
48 48 100 SAUV4 緯軒機電363.00
120 125 SPUVTD 緯軒機電430.001
1GO-245B.
Switch Number of Product List Price
Rating Switch Elements Number GO-135S
5A @ 240 Vac/ 1 b C SABAP1 緯軒機電154.00 0.5A @ 125 Vdc
Gold-Plated Contacts 1 b C SABAG1 緯軒機電154.00 0.5A @30V
Note: UL listed at 200,000 AIC without internal accessories, 100,000 AIC with internally mounted accessories.
Bell Alarm Switch
The bell alarm switch provides remote indication of whether the circuit breaker has been
tripped via open or closed SPDT switch elements, but remains unchanged during "On/Off"
circuit breaker operation and during operation by the "Push-to-Trip" button.
Undervoltage Release
Undervoltage Release
The undervoltage release provides automatic circuit breaker tripping when there is a
power loss or major dip (to 35%-70% of rated voltage) in accessory control voltage. AC
devices are UL listed for 50-60 Hz. Product number SAUV1 may be used with time delay
unit SPUVTD (List Price 緯軒機電430.00, GO-245B) (delay 0.1 to 1.0 seconds), 120 Vac b,
125 Vdc output.
Bell Alarm Switch
Purple
Yellow
Brown
Blue
Blue
All accessory contacts shown
with the circuit breaker in
tripped b.
All accessory contacts shown
with the circuit breaker in
tripped b.
Molded Case Circuit Breakers
Internal Accessories
Spectra? RMS Circuit Breakers
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-17
to change without notice
Contacts – Auxiliary and Bell Alarm (Rated 5A @240VAC, 0.5A @125VDC)
Normally Open Normally Closed
List Price List Price
Accessory Product No. GO-135H Product No. GO-135H
Aux. Switch Right Mounted FAS10RW 緯軒機電149.00 FAS01RW 緯軒機電149.00
Aux. Switch Left Mounted FAS10LW 緯軒機電149.00 FAS01LW 緯軒機電149.0
Bell Alarm Mechanism FABAM10W 緯軒機電154.00 FABAM01W 緯軒機電154.00
Releases – Shunt Trip and Undervoltage
Shunt Trip Undervoltage Release
Rating (Inrush List Price Rating (Inrush List Price
Voltage Power Consumption) Product No. GO-135H Power Consumption) Product No. GO-135H
12 VDC 200 mA / 2.4W FASHTBW 緯軒機電363.00 — ——
24 VAC/DC 100 mA / 3.6W FASHTDW 緯軒機電363.00 50 mA / 1.2W FAUVRDW 緯軒機電363.00
48 VAC/DC 60 mA / 2.88W FASHTFW 緯軒機電363.00 20 mA / 0.96W FAUVRFW 緯軒機電363.00
120 VAC 40 mA / 4.8W FASHTKW 緯軒機電363.00 — ——
110/130 VAC/DC 40 mA / 4.8W FASHTJW 緯軒機電363.00 15 mA / 1.8W FAUVRJW 緯軒機電363.00
220/240 VAC, 250 VDC 20 mA / 4.6W FASHTNW 緯軒機電363.00 15 mA / 3.45W FAUVRNW 緯軒機電363.00
277 VAC 11 mA / 3.0W FASHT7W 緯軒機電363.00 15 mA / 4.0W FAUVR7W 緯軒機電363.00
400/480 VAC 20 mA / 8.4W FASHTUW 緯軒機電363.00 15 mA / 6.3W FAUVRUW 緯軒機電363.00
Auxiliary Switch/Bell Alarm Mechanism
Shunt Trip/Undervoltage Release
Molded Case Circuit Breakers
Accessories
Record Plus? FC 100
Lugs and Lug Kits
Single Lug List Price Lug Kit List Price
Amp Range Wire Range Strip Length Product No. GO-135H Product No. (Set of 3) GO-135H
15-20A 14-10 Cu/Al .40-.50” FCAL12 緯軒機電3.25 FCALK12 緯軒機電9.00
25-60A 10-4 Cu/Al .40-.50” FCAL13 緯軒機電3.25 FCALK13 緯軒機電9.00
70-100A 4-1/0 Cu/Al .40-.50” FCAL14 緯軒機電3.25 FCALK14 緯軒機電9.00
External Accessories
Components: Parts
1
1-18 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Molded Case Circuit Breakers
Accessories
Record Plus? FE 250
FE Rating Plugs List Price
Trip Curve CT Rating Rated Current Product No. GO-135H
25A 20 A FERP3B0020 緯軒機電106.00
25 A FERP3B0025 緯軒機電106.00
30 A FERP3D0030 緯軒機電106.00
40 A FERP3D0040 緯軒機電106.00 60A 50 A FERP3D0050 緯軒機電106.00
60 A FERP3D0060 緯軒機電106.00
70 A FERP3G0070 緯軒機電106.00
80 A FERP3G0080 緯軒機電106.00
DES-200 90 A FERP3G0090 緯軒機電106.00 125A 100 A FERP3G0100 緯軒機電106.00
110 A FERP3G0110 緯軒機電106.00
125 A FERP3G0125 緯軒機電106.00
150A 150 A FERP3H0150 緯軒機電106.00
175 A FERP3K0150 緯軒機電106.00
200 A FERP3K0200 緯軒機電106.00 250A 225 A FERP3K0225 緯軒機電106.00
250 A FERP3K0250 緯軒機電106.00
Bell Alarm
Contact List Price
Configuration Contact Rating Wire leads Product No. GO-135H
1 NO (Form A) 5A @ 277 VAC, #16 AWG FABAM10W 緯軒機電154.00
0.3A @ 125 VDC
1 NC (Form B) 5A @ 277 VAC, #16 AWG FABAM01W 緯軒機電154.00
0.3A @ 125 VDC
UL Listed for field installation. Accessories are prewired from the factory with 36 inch long leads. Reference
instruction sheet DEH-40324 for wire lead colors.
Internal and External Accessories
Neutral Grounds and Sensors
Neutral Current Sensors
For grounded neutral system ground fault applications
List Price
Breaker Type Ampere Rating Product Number GO-135S
150 TSRG201 緯軒機電532.00
200 TSRG202 緯軒機電532.00
300 TSRG203 緯軒機電532.00 J 400 TSRG204 緯軒機電532.00
500 TSRG205 緯軒機電532.00
600 TSRG206 緯軒機電532.00
800 TSKG408 緯軒機電532.00
K 1000 TSKG410 緯軒機電532.00
1200 TSKG412 緯軒機電532.00 Neutral Current Sensor
Breaker Frames & Ratings Plugs
Insulated Case Circuit Breakers
Circuit Breakers History/Timeline
GE Insulated Case Circuit Breakers History/Timeline
1965 GE pioneered the design of insulated case circuit breakers when it introduced the original
Power Break? circuit breaker.
1995 GE introduced Power Break? II insulated case circuit breakers, the vanguard of a new age in reliable, flexible
and easy-to-use circuit protection.
Evolution of the GE Trip Unit
1965 Dual Magnetic Trip
1975 VersaTrip Solid State Trip
1979 VersaTrip Mod 2 Solid State Trip
1979 Magnetrip-Dual Mag
1979 SelecTrip
1982 MicroVersaTrip?
1988 MicroVersaTrip? RMS 9
1989 MicroVersaTrip? RMS 9 / Epic
1994 MicroVersaTrip? Plus/PM
1995 Enhanced MicroVersaTrip? Plus/PM
1996 Power Break? II MicroVersaTrip? Plus/PM
1997 Power Break? II Powerplus
2009 EnbliGuard? TU
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-19
to change without notice
This catalog contains replacement parts, retrofits, accessories,
and older generation products. For current generation products,
please see the GE BuyLog? or Control Catalog.
Components: Parts
1
1-20 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Enhanced MicroVersaTrip?, Rating Plug Selection
Power Break? II Rating Plug Selection
Enhanced
MicroVersaTrip? Plus
Power+ Trip and Enhanced
Power+ Trip Unit Ground MicroVersaTrip? PM
Unit Standard Fault Rating Trip Unit
Frame Sensor Current Rating Plugs Plugs Rating Plugs
Size Rating Rating List Price 緯軒機電89.00 List Price 緯軒機電747.00 List Price 緯軒機電89.00
(Amperes) (Amperes) (Amperes) GO-245A GO-245A GO-245A
100 TR2C100 TR2C100GF TR2B100
200 150 TR2C150 TR2C150GF TR2B150
200 TR2C200 TR2C200GF TR2B200
150 – – TR4B150
800 200 TR4C200 TR4C200GF TR4B200
225 TR4C225 TR4C225GF TR4B225 400 250 TR4C250 TR4C250GF TR4B250
300 TR4C300 TR4C300GF TR4B300
400 TR4C400 TR4C400GF TR4B400
300 – – TR8B300
400 TR8C400 TR8C400GF TR8B400
450 TR8C450 TR8C450GF TR8B450
800-1600 800 500 TR8C500 TR8C500GF TR8B500
600 TR8C600 TR8C600GF TR8B600
700 TR8C700 TR8C700GF TR8B700
800 TR8C800 TR8C800GF TR8B800
400 – – TR10B400
1000 600 TR10C600 TR10C600GF TR10B600
800 TR10C800 TR10C800GF TR10B800
1000 TR10C1000 TR10C1000GF TR10B1000
1600 600 – – TR16B600
800 TR16C800 TR16C800GF TR16B800
1600 1000 TR16C1000 TR16C1000GF TR16B1000
1100 TR16C1100 TR16C1100GF TR16B1100
1200 TR16C1200 TR16C1200GF TR16B1200
1600 TR16C1600 TR16C1600GF TR16B1600
750 – – TR20B750
800 – – TR20B800
1000 TR20C1000 TR20C1000GF TR20B1000
2000 2000 1200 TR20C1200 TR20C1200GF TR20B1200
1500 TR20C1500 TR20C1500GF TR20B1500
1600 TR20C1600 TR20C1600GF TR20B1600
2000 TR20C2000 TR20C2000GF TR20B2000
400 – – TR10B400
600 TR10C600 TR10C600GF TR10B600 1000 800 TR10C800 TR10C800GF TR10B800
1000 TR10C1000 TR10C1000GF TR10B1000
750 – – TR20B750
800 – – TR20B800
1000 TR20C1000 TR20C1000GF TR20B1000 2500 2000 1200 TR20C1200 TR20C1200GF TR20B1200
1500 TR20C1500 TR20C1500GF TR20B1500
1600 TR20C1600 TR20C1600GF TR20B1600
2000 TR20C2000 TR20C2000GF TR20B2000
1600 TR25C1600 TR25C1600GF TR25B1600
2500 2000 TR25C2000 TR25C2000GF TR25B2000
2500 TR25C2500 TR25C2500GF TR25B2500
1200 – – TR30B1200
1600 – – TR30B1600
3000 3000 2000 TR30C2000 TR30C2000GF TR30B2000
2500 TR30C2500 TR30C2500GF TR30B2500
3000 TR30C3000 TR30C3000GF TR30B3000
1600 TR40C1600 TR40C1600GF TR40B1600
2000 TR40C2000 TR40C2000GF TR40B2000
4000 4000 2500 TR40C2500 TR40C2500GF TR40B2500
3000 TR40C3000 TR40C3000GF TR40B3000
3600 TR40C3600 TR40C3600GF TR40B3600
4000 TR40C4000 TR40C4000GF TR40B4000
MicroVersaTrip? and MicroVersaTrip? PM Rating Plug
Trip Indicator Product List Price
L/ST/1 Ground Fault Number GO-245A
– – TARGET00 緯軒機電60.00
? – TARGET01 緯軒機電140.00
? ? TARGET02 緯軒機電160.00
Power+ Target Module
Power+ trip units are designed to accept an optional field-installable
target module. The target module indicates long-time pickup, battery
status, trip unit health status, and whether a breaker trip was
caused by an overload, a short circuit or a ground fault. Target
?modules are available with or without ground fault indication.
Power+ Trip Target Module
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-21
to change without notice
Ratings Ratings Field Installable List Price Factory Installed List Price
Vac Vdc Product Number GO-245B Product Number GO-245B
120 – SPE120R 緯軒機電1671.00 SPE120 緯軒機電1838.00
240 – SPE240R 緯軒機電1869.00 SPE240 緯軒機電2056.00
– 24 SPE024R 緯軒機電1869.00 SPE024 緯軒機電2056.00
– 48 SPE048R 緯軒機電1869.00 SPE048 緯軒機電2056.00
– 72 SPE072R 緯軒機電1869.00 SPE072 緯軒機電2056.00
– 125 SPE125R 緯軒機電1869.00 SPE125 緯軒機電2056.00
Ratings Ratings Field Installable List Price Factory Installed List Price
Vac Vdc Product Number GO-245B Product Number GO-245B
120 – SPRCS120R 緯軒機電286.00 SPRCS120 緯軒機電315.00
240 – SPRCS240R 緯軒機電286.00 SPRCS240 緯軒機電315.00
– 24 SPRCS024R 緯軒機電286.00 SPRCS024 緯軒機電315.00
– 48 SPRCS048R 緯軒機電286.00 SPRCS048 緯軒機電315.00
– 72 SPRCS072R 緯軒機電286.00 SPRCS072 緯軒機電315.00
– 125 SPRCS125R 緯軒機電286.00 SPRCS125 緯軒機電315.00
Electrical Operator
Remote Close Solenoid
This accessory provides an electrically operated solenoid which, when energized, closes
the breaker. It is suitable for control interlock schemes in which manual closing capability
would not be convenient or desirable. The breaker is provided with a manual close
button, which can be replaced by the Hidden "ON" Button accessory and/or sealed using
the Limited Access Pushbutton Cover accessory. The remote close accessory is continuously
rated and has an anti-pump feature, which prevents a motor operated breaker
from repeatedly closing into a fault. Closing control voltage must be removed and re-applied
for each breaker closure.
Remote Close Solenoid
Accessories—Stationary and Draw-out Breakers
The complete line of Power Break? II breaker accessories may be either factory or field
installed to meet user needs. The electronic shunt trip, the bell alarm, the bell alarm with
mechanical lockout, and the undervoltage release modules are drop-in from the front of
the breaker, interchangeable across all frames, and require no field internal wiring or
breaker disassembly. Auxiliary switch modules are available in groups of 4, 8 or 12,
NO/NC single-pole, double-throw (SPDT) switches. Their installation simply involves
removal of breaker cover, installation of the switch module, routing of wiring and installation
of the pre-wired terminal block and re-installation of the cover. Auxiliary switches
are also interchangeable across all Power Break? II breaker frames.
Electrical Operator
The electrical operator mounts inside the front cover of the manually operated breaker.
This accessory can be added to any Power Break? II breaker in the factory or the field
to provide electrical spring charging and charge indication. For remote closing, the
remote close solenoid must be priced and ordered separaby. All breakers are
prewired to dedicated secondary terminals for easy field installation. When electrical
operation is used, either a shunt trip or an undervoltage release must be ordered and
priced separaby.
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Stationary and Draw-out Breaker Accessories
All devices UL Listed for factory or field installation except where noted.
Components: Parts
1
1-22 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Shunt Trip
The shunt trip accessory is an electronic module, which provides remote control capability
to open the circuit breaker. When activated, the shunt trip module sends a signal to
the trip unit to open the breaker. This allows the trip unit to record, display, distinguish
and communicate (in MicroVersaTrip? PM trip units) that the opening event was initiated
by the shunt trip device. The shunt trip is continuously rated and requires no cut-off
switch. When energized, the shunt trip supplies +24Vdc power to the trip unit to power
the display.
Ratings Ratings Field Installable List Price Factory Installed List Price
Vac Vdc Product Number GO-245B Product Number GO-245B
– 12 SPST012R 緯軒機電301.00 SPST012 緯軒機電328.00
24 24 SPST024R 緯軒機電301.00 SPST024 緯軒機電328.00
48 48 SPST048R 緯軒機電301.00 SPST048 緯軒機電328.00
120 125 SPST120R 緯軒機電301.00 SPST120 緯軒機電328.00
208 – SPST208R 緯軒機電301.00 SPST208 緯軒機電328.00
240 250 SPST240R 緯軒機電301.00 SPST240 緯軒機電328.00
480 – SPST480R1 緯軒機電301.00 SPST4801 緯軒機電328.00
600 – SPST600R1 緯軒機電301.00 SPST6001 緯軒機電328.00
1Kit contains externally mounted transber.
Ratings Ratings Field Installable List Price Factory Installed List Price
Vac Vdc Product Number GO-245B Product Number GO-245B
12 SPSTL012R 緯軒機電401.00 SPSTL012 緯軒機電428.00
24 24 SPSTL024R 緯軒機電401.00 SPSTL024 緯軒機電428.00
48 48 SPSTL048R 緯軒機電401.00 SPSTL048 緯軒機電428.00
120 125 SPSTL120R 緯軒機電401.00 SPSTL120 緯軒機電428.00
208 – SPSTL208R 緯軒機電401.00 SPSTL208 緯軒機電428.00
240 250 SPSTL240R 緯軒機電401.00 SPSTL240 緯軒機電428.00
480 – SPSTL480R1 緯軒機電401.00 SPSTL480 緯軒機電428.00
600 – SPSTL600R1 緯軒機電401.00 SPSTL600 緯軒機電428.00
1Kit contains externally mounted transber.
Shunt Trip Module
Shunt Trip with Lockout Module
The shunt trip with lockout is identical to the regular shunt trip, but when energized, it
will also prevent closure of an "open" breaker by mechanically blocking both manual and
electrical closing. When energized, the closing springs will not discharge, the movable
contacts will not move; the contacts are "kiss free."
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Stationary and Draw-out Breaker Accessories
All devices UL Listed for factory or field installation except where noted.
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-23
to change without notice
Undervoltage Release Module
The undervoltage release is an electronic module used to open the circuit breaker when
the monitored voltage drops below 35-60% of its rated value. The undervoltage release
"resets" when the monitored voltage is re-established allowing the circuit breaker to reclose
(the sealing voltage of the UVR is 60-85% of its rated voltage).
An undervoltage release trip operation is produced by the MicroVersaTrip? Plus unit in
response to a signal from the undervoltage release module. This allows the trip unit to
record, display, distinguish and communicate (in MicroVersaTrip? PM trip units) that the
breaker opening event was due to undervoltage release. Operation of the undervoltage
release module will prevent breaker contact closure, i.e. "kiss-free" operation. When
energized, the undervoltage release supplies +24 Vdc power to the trip unit to power
the display.
Ratings Ratings Field Installable List Price Factory Installed List Price
Vac Vdc Product Number GO-245B Product Number GO-245B
24 – SPUV024ACR 緯軒機電301.00 SPUV024AC 緯軒機電328.00
48 – SPUV048ACR 緯軒機電301.00 SPUV048AC 緯軒機電328.00
120 – SPUV120ACR 緯軒機電301.00 SPUV120AC 緯軒機電328.00
208 – SPUV208ACR 緯軒機電301.00 SPUV208AC 緯軒機電328.00
240 – SPUV240ACR 緯軒機電301.00 SPUV240AC 緯軒機電328.00
480 – SPUV480ACR1 緯軒機電301.00 SPUV480AC1 緯軒機電328.00
600 – SPUV600ACR1 緯軒機電301.00 SPUV600AC1 緯軒機電328.00
– 12 SPUV012DCR 緯軒機電301.00 SPUV012DC 緯軒機電328.00
– 24 SPUV024DCR 緯軒機電301.00 SPUV024DC 緯軒機電328.00
– 48 SPUV048DCR 緯軒機電301.00 SPUV048DC 緯軒機電328.00
– 125 SPUV125DCR 緯軒機電301.00 SPUV125DC 緯軒機電328.00
– 250 SPUV250DCR 緯軒機電301.00 SPUV250DC 緯軒機電328.00
1Kit contains externally mounted transber.
Undervoltage Release Module
Bell Alarm (Alarm Only)
The bell alarm module is used to signal breaker "tripped" status to other accessories
(e.g., external alarm devices, indicating lights, relays, or logic circuits) for remote indication
and interlocking functions. The bell alarm response is configurable by means of
rear-mounted DIP switches on the trip unit. The bell alarm can be made to operate in
response to an overcurrent (including ground fault) or protective relay trip and/or a
shunt trip operation, and/or operation of the undervoltage release module. It is not
actuated as a result of normal breaker "ON/OFF" operation.
This module provides a visual, mechanical pop-out target, which protrudes through the
face of the circuit breaker door when it operates. The bell alarm may be reset manually
by depressing the mechanical target, or automatically by closing the breaker.
The bell alarm is provided with one SPDT switch with control power duty contacts as
shown in the auxiliary switch accessories.
Ratings Ratings Field Installable List Price Factory Installed List Price
Vac Vdc Product Number GO-245B Product Number GO-245B
240 125-250 SPBAA240R 緯軒機電124.00 SPBAA240 緯軒機電135.00
600 125-250 SPBAA600R1 緯軒機電124.00 SPBAA6002 緯軒機電135.00
2600 Vac module not UL Listed.
Bell (Alarm Only)
List Price
Debion Product Number GO-245B
Time Delay Module
(0.1 to 1.0 second delay) SPUVTD 緯軒機電430.00
Time Delay Module for UVR
The time delay module prevents nuisance tripping due to momentary loss of voltage.
The module has 120 Vac b and 125 Vdc output and must be used with the 125 Vdc UVR.
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Stationary and Draw-out Breaker Accessories
All devices UL Listed for factory or field installation except where noted.
Components: Parts
1
1-24 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Bell Alarm With Lockout
The bell alarm with lockout module combines both the bell alarm and a manual lockout
function. The bell alarm switch operates identically to the standard bell alarm module,
except that the mechanical pop-out target must be manually reset before the breaker
can be closed.
Operation of the bell alarm with lockout module can be independently set by means
of setting the DIP switches at the rear of the trip unit. Current rating of the single SPDT
switch is identical to the auxiliary switch accessories.
Ratings Ratings Field Installable List Price Factory Installed List Price
Vac Vdc Product Number GO-245B Product Number GO-245B
240 125-250 SPBAL240R 緯軒機電124.00 SPBAL240 緯軒機電135.00
600 125-250 SPBAL600R1 緯軒機電124.00 SPBAL6001 緯軒機電135.00
1600 Vac module not UL Listed. Bell Alarm with Mechanical Reset Lockout
Auxiliary Switch
An auxiliary switch signals the circuit breaker’s primary contact b (i.e., OPEN or
CLOSED) to other devices, such as indicating lights, relays or logic circuits. This enables
the user to provide remote indication, interlocking or control operations as a function of
breaker primary contact b. The auxiliary switch operation is independent of the
b by which the breaker is opened or closed. The auxiliary switch does not distinguish
between a "tripped" or "open" condition. The auxiliary switch contacts follow the
main breaker contacts on opening and precede them on closing.
Auxiliary switch modules are available with 4, 8 or 12 NO/NC (SPDT) switches for control
power duty ac/dc ratings. When ordered for field installation, an auxiliary switch module
comes pre-wired to its own terminal board, which mounts with one screw to the left of
the breaker. A special accessory, available for draw out breakers, comes pre-wired to the
?breaker secondary disconnect. All switch ratings are 6A at 120V-600 Vac, 1/2A at 125
Vdc and 1/4A at 250 Vdc.
Auxiliary Switches for Stationary Breakers
No. of SPDT
Ratings Ratings Switch Elements Field Installable List Price Factory Installed List Price
Vac Vdc (Contacts) Product Number GO-245B Product Number GO-245B
240 125-250 4 SPAS240AB4R 緯軒機電268.00 SPAS240AB4 緯軒機電293.00
240 125-250 8 SPAS240AB8R 緯軒機電564.00 SPAS240AB8 緯軒機電616.00
240 125-250 12 SPAS240AB12R 緯軒機電651.00 SPAS240AB12 緯軒機電710.00
600 125-250 4 SPAS600AB4R1 緯軒機電268.00 SPAS600AB41 緯軒機電293.00
600 125-250 8 SPAS600AB8R1 緯軒機電564.00 SPAS600AB81 緯軒機電616.00
1600 Vac module not UL Listed.
Auxiliary Switch with
Pre-wired Secondary Terminals
for Stationary Breaker
Auxiliary Switch with
Pre-wired Secondary Terminals
for Draw-out Breaker
Auxiliary Switches for Draw-out Breakers
No. of SPDT
Ratings Ratings Switch Elements Field Installable List Price Factory Installed List Price
Vac Vdc (Contacts) Product Number GO-245B Product Number GO-245B
240 125-250 4 SPAS240AB4DR 緯軒機電551.00 SPAS240AB4D 緯軒機電576.00
240 125-250 8 SPAS240AB8DR 緯軒機電847.00 SPAS240AB8D 緯軒機電899.00
240 125-250 12 SPAS240AB12DR 緯軒機電934.00 SPAS240AB12D 緯軒機電993.00
600 125-250 4 SPAS600AB4DR1 緯軒機電551.00 SPAS600AB4D1 緯軒機電576.00
600 125-250 8 SPAS600AB8DR1 緯軒機電847.00 SPAS600AB8D1 緯軒機電899.00
1600 Vac module not UL Listed.
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Stationary and Draw-out Breaker Accessories
All devices UL Listed for factory or field installation except where noted.
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-25
to change without notice
Mechanical Operations Counter
The mechanical operations counter is mounted behind the front cover of the breaker. It
is viewable through a rectangular knockout b opening in the breaker cover. It is a
five-digit, non-resettable counter, which is actuated each time the breaker is opened by
any means.
Field Installed List Price Factory Installed List Price
Product Number GO-245B Product Number GO-245B
SPCOUNTERR 緯軒機電100.00 SPCOUNTER 緯軒機電125.00
Hidden "ON" Button
The hidden "ON" button is assembled to the mechanism behind an unlabeled, false
?pushbutton. Manual closing of the breaker can only be perbed by means of a small
?diameter rod. This accessory is used to limit access to the manual "ON" control to
authorized personnel.
Field Installed List Price Factory Installed List Price
Product Number GO-245B Product Number GO-245B
SPPBNONR 緯軒機電64.00 SPPBNON 緯軒機電64.00
Maintenance/Repair Parts
Debion Product Number List Price GO Schedule
Top Cover and Rating Labels SPBII-REPLACE_COVER1 緯軒機電600.00 148C
Replacement MVT Door 10054335P1 緯軒機電20.00 148G
Replacement Powerplus Door 10054335P2 緯軒機電16.00 148G
Stop Block Kit w/Installation Tool SPBUMPERKIT 緯軒機電175.00 148C
Stop Block Kit (no tools) SPBUMPNTKIT 緯軒機電90.00 148C
1Special handling and order entry required to preserve UL Listing of breaker.
Contact Post Sale Service for additional details of special process.
Limited Access Pushbutton Cover
This accessory limits access to "ON/OFF" control of a breaker to authorized personnel.
The pushbutton cover accessory consists of transparent hinged covers that can be individually
sealed to the limited access assembly. Both the "ON" and "OFF" buttons can be
pilot drilled to allow use of a 1/8" rod to operate either one or both pushbuttons.
Field Installed List Price Factory Installed List Price
Product Number GO-245B Product Number GO-245B
SPPBCOVERR 緯軒機電80.00 SPPBCOVER 緯軒機電90.00
Mechanical Operations Counter
Breaker with limited access pushbutton
cover assembly installed
Activating the breaker closing
mechanism through the hole in the
Hidden “ON” Button
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Stationary and Draw-out Breaker Accessories
All devices UL Listed for factory or field installation except where noted.
Components: Parts
1
1-26 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Key Interlock Provisions
The key interlock provision enables the user to mount a one- to four-cylinder, narrowfaced,
Kirk-type FN or Superior customer-supplied lock on the face of the breaker. This
accessory provides mounting for key interlocks that are furnished by the customer. The
key interlock provision works in conjunction with the padlock provision. The key interlock
extends a lever through the padlock hasp when the key is turned to the key removal or
bolt extended b. Additionally, the accessory provides a hasp for mounting three
padlocks with 1/4" to 3/8" diameter shanks.
Padlock Provisions (Standard)
Padlocking provisions are standard on all Power Break? II circuit breakers. When the
breaker is in the open b, and the padlock hasp is raised at least 1/4", the breaker
?cannot be closed mechanically or electrically. The hasp accepts up to three padlocks
with 1/4" to 3/8" diameter shanks.
Walking Beam Interlocks—Stationary Breakers Only
Walking beam interlocks are mechanical devices used to prevent two adjacent circuit
breakers from both being in the "ON" or closed b at the same time. However, both
breakers can be in the "OFF" or open b.
Door Interlock
The door interlock provides interlocking of the circuit breaker compartment’s hinged
door so that the breaker must be in the "OFF" b before the door can be opened.
The door interlock is defeatable with a small tool to allow authorized access.
Circuit Breaker List Price
Envelope Size (Amperes) Product Number GO-245B
800, 1600 and 2000 SPWB20 緯軒機電1228.00
3000 SPWB30 緯軒機電1228.00
4000 SPWB40 緯軒機電1228.00
Product Numbers, Key Interlock Provisions
Circuit Breaker Number of Field Installed List Price Factory Installed List Price
Envelope Size (Amps) Key Locks Product Number GO-245B Product Number GO-245B
All 1 to 4 SPK4R 緯軒機電355.00 SPK4 緯軒機電426.00
Field Installed List Price Factory Installed List Price
Product Number GO-245B Product Number GO-245B
SPDILR 緯軒機電173.00 SPDIL 緯軒機電208.00
Key Interlock Kit (lock not included)
Door Interlock
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Stationary and Draw-out Breaker Accessories
All devices UL Listed for factory or field installation except where noted.
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-27
to change without notice
Lug Adapter Kits
Kits pre-mount to bus structure allowing cabling or bussing to be completed prior to
breaker mounting. Accepts either lugs or crimp-type connector terminals. Kit includes
adapter and hardware for either a three-pole line-side, or a three-pole load-side connection.
(Lugs not included).
Circuit Breaker Max Rating Product Lug Max. Cables Wire Range List Price
Envelope Size (Amperes) (Amperes) Number Per Kit Per Pole kcmil Cu/AI GO-245B
400 TPLUG106 1 1 (2) #2 2-600 緯軒機電18.50
600 TPLUG206 1 2 (2) #2 2-600 緯軒機電27.50 800 800 TPLUG308 1 3 (3) 300-750 緯軒機電32.00
800 TPLUG1084 1 3 3/0-800 緯軒機電23.00
1600 800 TPLUG1084 1 6 3/0-800 緯軒機電23.00
1600 TPLUG408 1 4 500-800 緯軒機電39.00
2000 TPLUG1084 1 6 3/0-800 緯軒機電23.00
2000 800 TSLUG08 9 3 3/0-800 緯軒機電274.00
1200 TSLUG12 12 4 3/0-800 緯軒機電296.00
1600 TSLUG16 15 5 3/0-800 緯軒機電345.00
2000 TSLUG20 18 6 3/0-800 緯軒機電383.00
3000 2500 TSLUG25 21 7 3/0-800 緯軒機電418.00
3000 TSLUG30 27 9 3/0-800 緯軒機電630.00
4000 4000 TSLUG40 27 9 3/0-800 緯軒機電1045.00
4For use with adapter kit only. See table above.
Frame Product Suitable for List Price
Rating (Amperes) Number use with up to: GO-245B
3 TPLUG108 Lugs or
800 TPLUGA08 3 crimp Lugs1 per pole 緯軒機電78.50
6 TPLUG108 lugs or
1600 TPLUGA162 6 crimp Lugs1 per pole 緯軒機電389.00
6 TPLUG108 Lugs or
2000 SPLUGA203 6 crimp Lugs1 per pole 緯軒機電487.00
1Anderson No. VCEL-075-12H1 or equivalent
2T-Studs - TP16FCA - included with adapter
3T-Studs - SP20FCA - included with adapter
Lug Kits
Kits accept Cu/AI wire and are suitable for direct mounting to the breaker. When ordering
Type TPLUG kits, order one kit per line or load pole. Example: A complete set of lugs
for the line side of an 800A frame, 400A trip breaker would be Qty 3-TPLUG106 lugs.
When ordering TSLUG kits order one kit per line or load side; TSLUG kits require use of
T-studs. Example: A complete set of lugs for a 3000A frame, 2500A trip breaker would be
Qty 1-TSLUG25. T-Studs would also be required.
2000 Ampere Power Break? II breaker with
SPLUGA20 lug adapter kit and 18 lugs
(TPLUG108)
Type TPLUG206
Type TPLUG408
Type TPLUG308
Type TSLUG20
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Stationary Breaker Mounting Kits
All devices UL Listed for factory or field installation except where noted.
Components: Parts
1
1-28 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
T-Studs
T-studs mount directly to the breaker, and can be rotated for either vertical or horizontal
bus connection. 4000 ampere T-studs are for vertical bus bars only. Product number
includes one stud. Both copper and aluminum T-studs are tin-plated.
Trimplate
Factory Installed Field Installable List Price
Product Number Product Number GO-245B
SPTRIMPLATE SPTRIMPLATER 緯軒機電64.00
T-Studs—Front Connected Breaker
Circuit Breaker Max. Rating List Price
Frame Size (Amperes) (Amperes) Product Number GO-245B
800 800 SP08FCA1 緯軒機電36.00
800 800 SP08FCC2 緯軒機電36.00
2000 800-2000 SP20FCA1 緯軒機電49.00
2000 800-2000 SP20FCC2 緯軒機電49.00
2500 2000 SPS20FCA1 緯軒機電48.75
2500 2500 SPS25FCC2 緯軒機電51.50
3000 3000 SPS30FCC2 緯軒機電181.50
4000 4000 SPS40FCC2 緯軒機電240.50
4000 4000 SPS40LFCC2,3 緯軒機電395.00
T-Studs—Back Connected Breaker
Circuit Breaker Max. Rating List Price
Frame Size (Amperes) (Amperes) Product Number GO-245B
2500 2000 SPS20BCA1,4 緯軒機電48.75
2500 2500 SPS25BCC2,4 緯軒機電51.50
3000 3000 2,5 緯軒機電181.50
1Aluminum
2Copper
3Extra long stud. Alternate with SPS40FCC for ease of installation.
4Six T-studs at no charge when ordered with breaker
5Supplied with integral T-stud
2000A Breaker with "T" Studs Mounted
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Stationary Breaker Mounting Kits, Wall Mounted Enclosures, Floor Mounted Enclosures
All devices UL Listed for factory or field installation except where noted.
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-29
to change without notice
MicroVersaTrip? Portable Test Kit
The test kit product number TVRMS2 is a portable, battery-powered,
test kit which provides for trip unit health checks and functional
trip and no-trip tests. It also provides defeat of the
ground-fault function and can be used in conjunction with highcurrent
test equipment. The test kit can be used to provide +24V
power to the trip unit for cold set-up and viewing of trip targets.
This test kit is for use with RMS-9, Epic, MicroVersaTrip? Plus and
MicroVersaTrip? PM trip units. The kit uses six rechargeable ni-cad
or standard alkaline "D" cells supplied by the customer. Kit can
also be powered by 120 Vac source.
List Price
Debion Product Number GO-245B
Portable Test Kit TVRMS2 緯軒機電3000.00
MicroVersaTrip? Portable Power Pack
The handheld MicroVersaTrip? portable battery pack provides
an independent power source for Enhanced MicroVersaTrip? Plus
and MicroVersaTrip? PM trip units as an alternative to the TVRMS2
test set. The power pack is used to power up the trip unit to set or
adjust trip set points when the breaker is on the bench or otherwise
not powered up. It connects to the trip unit through
the rating plug test jack. It requires three (3) standard 9 Vdc
alkaline batteries (not included).
List Price
Debion Product Number GO-245B
MicroVersaTrip? Plus and PM
Portable Power Pack TVPBP 緯軒機電75.00
POWER LEADER? Power Supplies
Power supply for furnishing 24Vdc control power for
MicroVersaTrip? Plus and PM trip units.
System Requirements Product List Price
Debion (price separaby) Number G0-104A
1.5 ampere power supply
Price one PLPS4G01 for
each line-up. 45 trip units Input power, 100VA
and 100 ft. maximum. (85-265Vac or 100-370Vdc) PLPS4G01 緯軒機電1250.00
POWER LEADER? Voltage Conditioner
Conditions and scales 120Vac to 1.76 Vac for use by the trip unit
for voltage sensing. Provides transient protection. Voltage conditioners
require isolation PTs.
System Requirements Product List Price
Debion (price separaby) Number G0-104A
Supplies isolated bus
voltage signal to One set of 3 voltage conditioners
MicroVersaTrip? PM required for each voltage sensing 緯軒機電200.00
trip units. b. PTs also required. PLVC1G01 per set
Neutral Current Sensors1
Circuit Breaker Neutral Sensor
Breaker Frame Sensor Rating Rating or Tap Product List Price
(Amperes) (Amperes) Settings (Amperes) Number GO-245B
200 200 TSVG302 緯軒機電266.00
800 400 400/200 TSVG304A 緯軒機電266.00
400 600/3002 TSVG306A 緯軒機電266.00
800-1600 800 800/400 TSVG308A 緯軒機電266.00
1000 800/4002 TSVG808A 緯軒機電266.00
1600 1000 1000/500 TSVG810A 緯軒機電266.00
1600 1200/6002 TSVG812A 緯軒機電266.00
1600 1600/1000 TSVG816A 緯軒機電266.00
2000 2000 2000/1000 TSVG820A 緯軒機電266.00
1000 800/4002 TSVG808A 緯軒機電266.00
1000 1000/500 TSVG810A 緯軒機電266.00
1000 1200/6002 TSVG812A 緯軒機電266.00
3000 1000 1600/10002 TSVG816A 緯軒機電266.00
2000 2000/1200 TSVG820A 緯軒機電266.00
2500 2500/1800 TSVG825A 緯軒機電266.00
3000 3000/2400 TSVG830A 緯軒機電266.00
4000 4000 4000/3000 TSVG940A 緯軒機電266.00
1Match neutral current sensor rating (or tap setting) to circuit breaker sensor rating.
2For use with multiple source ground fault protection schemes. Rating does not
match MicroVersaTrip? Plus or PM frame sensor.
Neutral Current Sensor
Rating Plug Removal Tool
List Price
Product Number GO-135S
TRTOOL 緯軒機電12.00
Reference
Instructions GEH-6492
Reference
Instructions GEH-5946
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Neutral Current Sensors and POWER LEADER Accessories
Components: Parts
1
1-30 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Features
—Draw-outs through 4000 amperes are UL Listed, 100% rated
—Modular design for simplified installation—6 basic sizes—800, 1600, 2000, 2500,
3000, 4000—5 inch pole centers
—Screw racking mechanism provides positive racking motion
—Self aligning primary and secondary disconnects
—Four b draw-out—engaged, test, disengaged, fully withdrawn—
simplifies system testing and inspection
—Breaker b indicator bly shows breaker b
—Provisions for padlocking breaker in test or disengaged b
—Mechanical interlock logic prevents movement of a closed breaker
—Suitable for reverse feeding
Debion
The draw-out assembly consists of a substructure housing unit designed as a compact
self-supporting unit and a draw-out breaker which must be ordered separaby. The
substructure contains mounting holes, self-supporting male plugs and extendable rails,
and can be ordered separaby for installation in your switchboard or enclosure.
The Power Break? II draw-out breaker is a self-contained, heavy-duty assembly designed
to offer simplified breaker inspection without de-energizing the main bus structure.
The draw-out breaker comes complete with racking mechanism drive, wheels, primary
and secondary disconnects and cooperating interlock systems.
Accessories such as dead-front shutters, by-pass switches (b switches), and
padlock devices are available and field installable.
OEM Substructures
Substructures are available for both standard and Hi-Break Power Break? II breakers.
Holes are provided for bolting on a shelf or supports. Holes are also provided in the primary
stabs for bolting to busbars or terminal lugs. Substructure secondary disconnects
are ordered and priced separaby. Order Hi-Break substructures for use with Power
Break? II switches.
Frame Rating Standard Break List Price Hi-Break List Price
(Amperes) Product Number GO-245B Product Number GO-245B
800 SPSDOS08 緯軒機電671.00 SPHDOS08 緯軒機電724.00
1600 SPSDOS16 緯軒機電1300.00 SPHDOS16 緯軒機電1403.00
2000 SPSDOS20 緯軒機電1892.00 SPHDOS20 緯軒機電2040.00
2500 SPSDOS25 緯軒機電2048.00 SPHDOS25 緯軒機電2207.00
3000 SPSDOS30 緯軒機電2739.00 SPHDOS30 緯軒機電2951.00
4000 SPSDOS40 緯軒機電6916.00 SPHDOS40 緯軒機電7455.00
List Price
Location Product Number GO-245B
Substructure SPDOSD36S 緯軒機電283.00
Breaker1 SPDOSD36B 緯軒機電283.00
1Order for replacement only. Included and factory wired with draw-out breaker.
Draw-out Breaker in Substructure
1600-ampere substructure for
standard break breaker
Secondary Disconnect for Draw-out Breakers
Control wiring is connected through draw-out secondary disconnects in the "TEST" and
?"CONNECTED" bs only. Up to 72 control circuits are possible through 36 b
plug-style secondary disconnect blocks factory mounted to each side of draw-out
breakers. One substructure disconnect (SPDOSD36S) must be ordered for each breaker
when accessories or communications are used. When auxiliary switches are used along
with any other electrical accessory or communications, two disconnects must be ordered.
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Draw-out Breaker Accessories
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-31
to change without notice
Racking Tool
The racking tool is a drive wrench with a square 1/2" socket
that engages the racking mechanism of the draw-out breaker.
One racking tool is supplied with every five draw-out breakers
at no charge.
List Price
Frame Rating Product Number GO-245B
All TDORT 緯軒機電70.00
Mechanical Interlocks
Mechanical interlocks provide the same function as the walking
beam accessory for stationary breakers, except they are used
with two draw-out breakers: mounted on common compartment
centerline, in either the same vertical section or adjacent vertical
sections.
List Price
Envelope Size Product Number GO-245B
800-2000 SPDOWB20 緯軒機電1310.00
2500-4000 SPDOWB40 緯軒機電1310.00
Rail Kit
This field installable rail kit may be used to shorten the two
standard OEM substructure rails by 3-1/2 inches.
List Price
Product Number GO-245B
SPRAILS 緯軒機電310.00
Position Switch
Provides positive indication when the draw-out breaker or switch
primary contact fingers have been fully withdrawn from the main
bus connections. Switch contacts change state only after the
primary fingers are fully disconnected when the breaker is being
moved from the CONNECTED b through the TEST b
and into the DISCONNECTED b.
May be used as part of a safety interlocking system in addition
to the visual indicator on the draw-out substructure. The Position
Switch accessory does not indicate either the TEST or CONNECTED
b. The switch assembly mounts on the stationary frame
and the actuator mounts to the carriage. Switch contacts are
rated at 10A at 600 Vac, 0.75A at 125 Vdc, and 0.25A at 250 Vdc.
Number of List Price
Switch Elements Product Number GO-245B
2 NO/2 NC SDOPS2L 緯軒機電177.00
4 NO/4 NC SDOPS4L 緯軒機電256.00
6 NO/6 NC SDOPS6L 緯軒機電336.00
Shutter Kit
This field installable kit provides shutters used to prevent unintentional
contact with potentially live primary disconnect stabs when
a breaker is racked out of an energized switchboard compartment.
List Price
Frame Rating Product Number GO-245B
800-2000A SPDSS20 緯軒機電501.00
3000A SPDSS30 緯軒機電501.00
4000A SPDSS40 緯軒機電501.00
By-Pass Switch
Provides positive indication that the draw-out breaker or switch
?primary contact fingers are fully connected to the main bus in the
substructure. Switch contacts change states only after the primary
fingers are fully connected when the breaker is being
moved from the DISCONNECTED b through the TEST b
and into the CONNECTED b.
May be used to provide control circuit continuity or downstream
?signaling that the draw-out breaker is connected in addition to
the visual b indicator on the draw-out substructure. The
By-pass switch accessory does not indicate either the TEST or
DISCONNECTED b. The switch assembly mounts on the stationary
frame and the actuator mounts to the carriage. Switch
contacts are rated at 10A at 600 Vac, 0.75A at 125 Vdc, and
0.25A at 250 Vdc.
Number of List Price
Switch Elements Product Number GO-245B
2 NO/2 NC TDOBP2L 緯軒機電177.00
4 NO/4 NC TDOBP4L 緯軒機電256.00
6 NO/6 NC TDOBP6L 緯軒機電336.00
Racking Padlock Provision
The racking padlock provides a means for the user to prevent racking
tool engagement, thereby preventing movement of the breaker
between the DISCONNECTED, TEST and CONNECTED bs.
List Price
Frame Rating Product Number GO-245B
All TDOPC 緯軒機電46.00
Lifting Bar
The lifting bar provides a means of safely lifting a draw-out circuit
breaker. A chain hook can be attached to the central hole in the
lifting bar or a 1" diameter black iron pipe can be put through the
two holes above the hooks, allowing two people to carry the
breaker below waist level from either side of the breaker.
One lifting bar is supplied with every five draw-out breakers at
no charge.
List Price
Frame Rating Product Number GO-245B
All TDOLB 緯軒機電104.00
Insulated Case Circuit Breakers
Power Break? II Circuit Breaker Accessories
Draw-out Breakers and Accessories
All devices UL Listed for factory or field installation except where noted.
Components: Parts
1
1-32 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Neutral Current (800: 1 ratio) Sensors
Inside Core Thermal Rating Weight Product List Price
Dimensions Construction (Amperes) (Lbs.) Number GO-142
2.5” Dia. Solid 1600 3 TGS0002 緯軒機電460.00
5” Dia. Solid 2500 4 TGS0005 緯軒機電731.00
8” Dia. Solid 3000 7 TGS0008 緯軒機電856.00
4” x 8” Split 4000 15 TGS0408 緯軒機電1439.00
8” x 8” Split 4000 25 TGS0808 緯軒機電1482.00
Neutral Current Sensor - Solid
Neutral Current Sensor - Split
Disconnect Switches and Operating Mechanisms
High-Pressure Contact Switch
With Integral Ground Fault Devices, 800-4000 Amperes, 600 Vac Max., UL File. No. E-51827
Components: Parts
1
Prices and data subject Aftermarket Catalog www.geelectrical.com 1-33
to change without notice
Field Installed Lugs Kits 800-1600 Ampere
Switches–Direct Mounting
Field installed only. Kits consist of lugs and hardware for direct
?mounting to switch terminal straps (multiple-hole tang lugs) or lugs
for mounting to 800 ampere terminal adapter kit. Order three kits
for three-pole line or load end. For 1600-ampere, copper conductors
must be used.
Ampere Rating Accessory Wire Range Product List Price
Type Cu/Al Number GO-145A
800A Lug Kit Line (3) 300-750 THPCLUG308 緯軒機電63.50 & Lug Kit Load
1200A, 1600A Lug Kit Line (4) 500-800 kcmil TPLUG408 緯軒機電39.001
1200A, 1600A Lug Kit Load (4) 500-800 kcmil THPCLUG408 緯軒機電77.50
1GO-245B
Field Installed Lugs Kits 2000-4000 Ampere
Switches–Direct Mounting
Field installed only. To terminate line and load cables, must be
used in conjunction with bus-connection adapter on page 7-20 (T
Studs). Each lug kit includes lugs, straps and hardware for threephase
line or load connections. Each cable lug accommodates
1–3/0 Cu or 250 kcmil Al to 800 kcmil Cu-Al. Accepts Anderson
VersaCrimp when lugs are removed from straps.
No. of Lugs per Pole Product List Price
Ampere Rating Line or Load End Number GO-245B
2000A 6 TSLUG20 緯軒機電383.00
2500A 7 TSLUG25 緯軒機電418.00
3000A 9 TSLUG30 緯軒機電630.00
4000A 11 TSLUG40 緯軒機電1045.00
Field Installed T Studs
Field installed only. May be used to adapt line and load terminals
of switch to vertical or horizontal bus arrangements. Three
required for line or load connections on three-phase bus. Accepts
either lugs, bolts, or Anderson VCEL VersaCrimp.
Basic Switch Product List Price
Rating (Amperes) Number GO-145A
800 THPC08FCA2 緯軒機電71.00
1200-1600 TP16FCA 緯軒機電113.00
2000 TS20FCA 緯軒機電113.00
2500 TS25FCA 緯軒機電119.00
3000 TS30FCA 緯軒機電418.00
4000 (5)TS40FCA 緯軒機電562.00
4000 (1)TS40LFCA3 緯軒機電789.00
2For vertical bussing only.
3For center pole, line terminal.
Disconnect Switches and Operating Mechanisms
High-Pressure Contact Switch
Accessories, UL Listed
Section 2: Switchgear
Table of Contents
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-1
to change without notice
History/Timeline .............................................................................2-2
Low Voltage Power and DC Circuit Breakers .............................2-3
Gerapid High Speed DC Circuit Breakers ..........................................2-3
AK and AKR Low Voltage Power
Circuit Breakers.........................................................................................2-4
Trip Unit Conversion Kits...........................................................................2-5
Overview – EnbliGuard? TU and ProTrip?
Conversion Kits.....................................................................................2-5
ProTrip? Trip Unit Conversion Kits Selection Guide ...............2-7
ProTrip? Rating Plugs.........................................................................2-11
EnbliGuard? TU Trip Unit Conversion
Kits Selection Guide.........................................................................2-12
EnbliGuard? TU Trip Rating Plugs................................................2-16
EnbliGuard? TU Trip Unit Conversion Kit
Accessories and Hardware..........................................................2-17
Trip Unit Conversion Kit Accessories ...........................................2-18
Electrically Operated Racking Device .............................................2-20
Technical Specifications.....................................................................2-21
Reference Publications............................................................................2-22
Asbestos Free Arc Quencher Replacement Kits..........................2-23
This catalog contains replacement parts, retrofits, accessories,
and older generation products. For current generation products,
please see the GE BuyLog? or Control Catalog.
Switchgear
2-2 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
Low Voltage Switchgear History/Timeline
GE Low Voltage Switchgear History/Timeline
1930’s-50 AE/AL Manufactured from 1930’s(?) to the early 1950’s
1951-75 AKD
AK = Power Circuit Breaker Equipment
D = Drawout circuit breaker construction
Manufactured 1951 - 1975, all bolted copper bus design, all breakers drawout, AK-1, 2, 3 - 15 / 25 / 50 / 75 / 100.
4000A max bus rating, 4 levels of bus, ring bus used in all feeder sections, main bus has provisions for future extension,
sections in outdoor construction did not line up in the front, indoor construction has extended frames to allow
the fronts of the sections to align. Indoor depths 49” (225 / 600A breakers), 59” (1600A breakers), 63” (3200 / 4000A
breakers). Breakers had ratcheting drawout mechanism – open door drawout. Painted ANSI 61 light gray, manufactured
in Philadelphia 1951 - mid-60’s, Bbington mid-60’s - 1975. Breaker compartment was a welded assembly,
equipment frame was bolted. Breaker boxes were stacked to make a vertical section with equipment frame around
the breaker boxes. No bus compartment barriers, open bus design. Ring silver plating on bolted connections.
1951-60’s AKS Stationary version of AKD, manufactured 1951 - 60’s
1960-77 AKD-5 Manufactured 1960 - 1977, aluminum bus with “flash-butt welded” copper to aluminum at bolted connections.
AK-2A, 3A -25 / 50 / T50 / 75 / 100 (“A” signifies AKD-5 drawout). Pull-lanyard drawout mechanism on early
design, replaced by single jackscrew mechanism and then replaced by double jack-screw mechanism. Closed-door
drawout with inner house breaker compartment. 60” deep frame with 18” extension option. Outdoor protected
aisle uses 60” deep indoor frame. Two bus levels available, ring bus used at 4000A. Welded / riveted frame, bus
compartment barriers, line/load separation barriers on mains and ties, isolation barriers on transber transitions,
copper runbacks on feeder breakers, ring silver plating on copper, aluminum bus unplated (welded connections).
Painted sand gray (beige), some instrument doors painted blue. AKR-30/50 in 22” wide sections introduced
in AKD-5 construction in early -70’s.
1977-81 AKD-6 Manufactured in Salisbury, NC 1977 - 1981. Some AKD-5 construction built in Salisbury ’75 - ’77 and nameplated
as AKD-6. No flash-butt welded aluminum to copper. Aluminum bus is tin plated and bolted at shipping splits (welded
everywhere else). Copper bus design has ring silver plating at bolted joints. Introduced AKR-75 / 100. Stab-and-finger
connections on 3200 and 4000A breakers versus round primary disconnect on AKD-5. Uses inner-house drawout breaker
compartment. Tuning fork primary disconnect (extrusion) on 800 - 2000A breaker compartments. Copper feeder breaker
runbacks. 60” deep frames with 18” optional rear extension. Painted ANSI 61 light gray. Breakers have ECS or SST trip units.
1981- AKD-8 Manufactured 1981 to present. Model 1 & 2 has extruded vertical bus. Model 2 introduced in 1983 to accommodate
present automated wiring programs and harness routing. Model 3 introduced in 1991 using flat bar vertical bus. Breakers use
MicroVersa Trip 9, RMS9, EPIC, MVT Plus, MVT PM trip units. Aluminum bus removed from design in 1996 in favor of standard
tin-plated copper bus (silver plating optional). Field convertible space compartment design added to allow empty
compartments to be modified to functioning breaker compartment without modifications to vertical bus.
1998- AKD-10 Introduced March 1998 as the successor to AKD-8. Manufactured along with AKD-8 for 1998 and 1999. Uses only
present WavePro low voltage power circuit breakers. Same dimensions as AKD-8. Only changes from AKD-8 are in the front breaker
compartment — new drawout rails, breaker door, secondary disconnects instrument panel. No need for Remote Display
for trip unit since WavePro breaker has trip unit in the escutcheon. AKD-10 can match & line-up with AKD-8 without a transition
(for indoor and outdoor construction). Same bus structure, frame, options, layouts and breaker stacking as AKD-8.
2005- Enblisys Introduced October 2005 as a new platb for low voltage switchgear. Uses non-automatic EnbliGuard
present breakers (similar to WavePro except no current sensors, no trip unit, and limited accessories). Enblisys uses redundant
components for highest reliability and maximum up-time. Redundant CPU’s perb all protection, metering, control,
and monitoring functions. Other redundant components of the system include 2 UPS’s, 2 network communication
switches for internal communication, 2 control power throwover relays, 2 control power sources (120vAC). Each breaker
cubicle is provided with an EnbliGuard Messenger, which is the interface between the CPU’s and the circuit breaker
operating mechanisms. The Messenger perbs A/D and D/A conversions plus provides back-up overcurrent proteciton
for the breaker if all control power and communications are lost.
Equipment construction is the same as AKD-10 switchgear (frame, bussing, drawout cubicles, etc). Enblisys does
not replace AKD-10. Both product lines are currently being produced.
2
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-3
to change without notice
Low Voltage Power and DC Circuit Breakers
Gerapid High Speed DC Circuit Breakers
Technical Data for Rectifier Circuit Breaker Models 8007R and 10007R
Breaker type Gerapid 8007R Gerapid 1007R
Arc chute type 1x2 1x3 1x2 1x3
Rated current In/A 6,000 6,000 8,000 8,000
Rated operating voltage Ue/V 800 1,200 800 1,200
Rated insulation voltage Ui/V 2,000 2,000 2,000 2,000
120 min./A 7,200 7,200 9,600 9,600
Short time current 2 min./A 8,000 8,000 16,000 16,000
20 sec./A 12,000 12,000 24,000 24,000
Mechanical endurance ops. 10,0001 10,0001 10,0001 10,0001
Total weight approx. kg 220 220 220 220
1With regular maintenance 100,000 ops.
Figure 3. Gerapid 8007R and 10007R Rectifier CB, 1X2 Arc Chute, 800VDC
(Dimensions in mm)
Switchgear
2
2-4 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
AK and AKR Low Voltage Power Circuit Breakers
New AK and AKR low voltage power circuit breakers are available for replacement and
retrofill needs. The following circuit breakers are available:
AK Circuit Breaker
AC Voltage Rating Frame Size Short-circuit Ratings — RMS Symmetrical KA
60 Hertz Breaker Type (Amps) With Instantaneous Trip Without Instantaneous Trip
AK-25 600 22 22
600 AK-50 1600 42 42
AK-50H 1600 65 65
AK-25 600 30 22
480 AK-50 1600 50 50
AK-50H 1600 65 65
AK-25 600 42 22
240 AK-50 1600 65 50
AK-50H 1600 85 65
AKR Circuit Breaker
AC Voltage Rating Frame Size Short-circuit Ratings — RMS Symmetrical KA
50/60 Hertz Breaker Type (Amps) With Instantaneous Trip Without Instantaneous Trip
AKR-30 800 30 30
AKR-30H 800 42 42
600 AKR-50 1600 42 42
AKR-50H 1600 65 65
AKRT-50H 2000 65 65
AKR-75 3200 65 65
AKR-100 4000 85 85
AKR-30 800 30 30
AKR-30H 800 42 42
480 AKR-50 1600 50 50
AKR-50H 1600 65 65
AKRT-50H 2000 65 65
AKR-75 3200 65 65
AKR-100 4000 85 85
AKR-30 800 42 30
AKR-30H 800 50 42
240 AKR-50 1600 65 50
AKR-50H 1600 65 65
AKRT-50H 2000 65 65
AKR-75 3200 85 65
AKR-100 4000 130 85
Contact your local GE sales representative for price and delivery. Be prepared to provide full
nameplate data from your existing low voltage switchgear lineup.
AK-25 Breaker
AKR-30H Breaker
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-5
to change without notice
AK-25 Breaker with EnbliGuard? TU Trip Unit
Low Voltage Power and DC Circuit Breakers
Trip Unit Conversion Kits
EnbliGuard? TU Conversion Kits
GE offers a complete line of trip unit upgrade kits for low voltage
power circuit breakers manufactured by GE, as well as by
Westinghouse, I-T-E, and Allis-Chalmers. These conversion kits
contain everything necessary to convert an old-style electromechanical
or solid-state trip unit to today's latest electronic,
digital technology—including the addition of metering, protective
relay, waveb capture, RELT, and communication functions.
All conversion kits designed by GE are tested to ANSI C37.59
standards for each breaker type so customers have the
assurance of safe, reliable operation.
Features and Benefits–All Kits
—Kit includes everything needed in one compact package
—Full-range of interchangeable rating plugs
—Trip targets for quick identification of overload, short circuit,
and ground fault trips
—Sealable, see-through cover to prevent unauthorized access to
trip unit settings
—Portable Trip Unit Test Kits; GTUTK20 and TVRMS2
—Eliminate costly downtime due to nuisance tripping
—Improved power system coordination and protection
—Extend life and function of existing breakers and low voltage
equipment
EnbliGuard? TU Conversion Kits
—True RMS sensing with a sampling rate of 48 samples per cycle
with the ability to Waveb capture 4 cycles prior and 4 cycles
after an event
—Long Time, Short Time, and Instantaneous Standard on all trip
units. S and I switchable on ANSI breakers
—Large backlit LCD screen, view all currents on one screen
—Trip settings and trip target inbation stored in non-volatile
memory
—On-board lithium battery (field replaceable) for cold set-up and
reading trip targets
—Status and Event Log, view the last 10 events
—Health Status LED and Thermal Memory
—Comm port for interface with set-up software and to download
Waveb
—Optional metering, relaying, communications, ZSI - I, ground
fault (trip & alarm), and fused shaped curves
—Plug and Play with previous generation of RMS9, EPIC, MVT and
Enhanced MVT Trip Units
ProTrip? Conversion Kits
—Cost-effective upgrade with standard adjustable long time,
short time, instantaneous, and defeatable ground fault functions
—Simple-to-use rotary switches for selecting the trip unit pickup
and delay settings
—True RMS sensing with sampling rate of 48 times per cycle
per phase - accurate waveb measurements through the
11th harmonic
—Standard target module with individual LEDs for overload pickup,
overload trip, short circuit trip, ground fault trip, and target
module battery monitor
Everything You Need in One Package
ProTrip? and EnbliGuard? TU conversion kits for the breakers
listed in the following pages are shipped complete with detailed
installation instructions and everything needed for fast and easy
trip unit conversions.
—Digital solid-state trip with quick disconnect
—Direct-acting flux shift trip actuator with automatic reset
—Epoxy encapsulated high-accuracy current sensors
—Interchangeable rating plug (order separaby)
—Specially designed mounting hardware and wire harnesses for
each breaker frame
Switchgear
2
2-6 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
Trip Unit Conversion Kits
EnbliGuard? TU Trip Unit
EnbliGuard? TU Conversion Kits—
Upgrade your low-voltage equipment with
electronic trip unit technology.
Normal wear and tear of aging electro-mechanical trip devices
on low-voltage circuit breakers increases susceptibility to loss of
calibration that can subsequently jeopardize electrical power
system coordination, protection and reliability.
GE has channeled its decades of circuit breaker trip system
experience into the development of the EnbliGuard? TU Trip Unit.
The EnbliGuard? TU builds on the past trip units by incorporating
advance algorithms that enable Arc Flash protection and
Selectivity at the same time.
ANSI C37.59 design verification tested to ensure safe, reliable
operation, these kits are designed to extend the life of your
mechanically sound breaker and…
—Eliminate costly downtime due to nuisance tripping. Improves
on past trip units with a Waveb Recognition Instantaneous
Algorithm
—Improve electrical power system coordination and protection
—Permit easy upgrades to communicating Power Management
Control Systems (PMCS), open Modbus RTU protocol
—Enable the implementation of RELT and Zone Selective Interlock
Instantaneous to reduce Arc Flash Energy Levels.
Standard Features
—Flexible Time Current Settings
—I
2T Long Time, Long Time Delay
—Short Time, Short Time Delay, 3 Short Time I2T Slopes
—Waveb Recognition Instantaneous
—Ammeter
—Large Backlit LCD Screen1
—Date and Time1
—Breaker Status Indication
—Universal Rating Plugs
—Status and Event Log (10 Events)
—LED Health Status Indicator1
—Set-up Software
—I/O – 1 Input and 1 Output1
—Thermal Memory, Battery Back-up
—Common Interface across all versions
Optional
—Internal/External Ground Fault Trip or Alarm with 4 curves to
select from (I2T, I4T, SGF, Definite Time Slope)1
—Switchable Ground Fault Trip / Alarm (not UL Listed)
—Fused Long Time Curves (I4T)
—Modbus Open RTU Communications1
—Waveb Capture – Enables Harmonic analysis
—Full-function Metering1
—Protective Relaying1
—Zone Selective Interlock – GF, S, I1
—RELT – Reduce Energy Let Through1
—RELT and Ground Fault Alarm Harness Kits
—Test Set GTUTK20
Test Kit – GTUTK20
Arc Flash and Selectivity at the same time
The EnbliGuard? TU Trip Unit offers optimum circuit protection
and optimum system reliability simultaneously with little or no
compromise to either of these critical functions. Reliability and arc
flash protection, in one package, at the same time, all the time.
Algorithms enabling arc flash protection and selectivity
—RELT – Reduced Energy Let Through
—Zone Selective Interlocking – Instantaneous (ZSI-I)
—Waveb Recognition Instantaneous – Coordinate with Current
Limiting Devices and reduces Nuisance Trips
—Flexible Time Current Curves – Create the shape you need
Reliability – Health Status
—Non-volatile memory with continuous self-testing microprocessor
—Health Status LED indicates Normal Operation, Errors, Pick-up, Trip
—External Power Not Required with Long Life Lithium Battery
—Positive setpoint recognition, values flash until saved
Plug and Play
—Same Form, Fit, Function as the popular MicroVersaTrip? Trip
Unit. Easily upgrade an existing converted breaker1
Optional Full-function metering including
—current (Amps, kAmps)
—voltage (Ph-Ph, Ph-N)
—energy (kWh, MWh, GWh)
—real power (kW, MW)
—total power (kVA, MVA)
—frequency (Hz)
—demand (avg. kW, MW) and peak demand
Optional protective relaying functions include
—undervoltage
—overvoltage
—voltage unbalance
—current unbalance
—power reversal
—power direction setup
1Note: Some options require 24VDC, additional hardware to enable Metering,
Relaying, RELT, ZSI, Modbus to be added to the Breaker, Equipment Cubicle,
and Equipment Sections.
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-7
to change without notice
Low Voltage Power and DC Circuit Breakers
ProTrip? Trip Unit Conversion Kit Selection Guide
For GE Circuit Breakers
Product Number Structure
PK115 3 F 01 08 D
Breaker
AK-1-15
AK-15
AK-1-25
AK-25
?AKU-25
AK-1-50
?AK-50
AKU-502
?AKT-50
AKS-50
AKSU-502
?AKST-50
AK-753
?AK-1003
Wiring
?3 Wire-3
?4 Wire-4
Sensor Type
?Fixed CTs-F
For converting AK-2 version breakers and newer, not applicable for AK-1 or AKR
Breakers equipped with older style open fuse lockout devices (OFLO), must be
retrofitted with newer style OFLO device prior to conversion process.
Order replacement OFLO kits as follows: AKU-50 - order OFLO kit #121C287OG2,
AK-75 - order OFLO kit #121C287OG3, AK-100 - order OFLO kit #121C287OG4
Contact the factory for stationary breaker applications
Trip Functions
LSIGX- 08
Trip Unit Functions
LSIGX- Long Time, Short Time/INST.
?and Switchable Ground Fault (off)
?Not Approved for a UL Listed Breaker
Model
Generation-D
Sensor Rating
150A- 01
?225A- 02
?600A- 06
?800A- 08
?1600A- 16
?2000A- 20
?3000A- 30
?4000A- 40
Sensor Rating Selection
?Frame Breaker Product Numbers Sensors
PK115
PKO151
PK125
PKO753
PKO501
PK150
PKO251
PKO103
225 AK-1-15, AK-15 150A, 225A
600 AK-1-25, AK-25, AKU-25 150A, 225A, 600A
?AK-1-50, AK-50, AKU-50,
?AKS-50, AKSU-50
2000 AKT-50, AKST-50 2000A
3000 AK-75 3000A
4000 AK-100 4000A
1600 800A, 1600A
1
2
3
ProTrip? Conversion Kits
List Price
Frame Size (Amps) Breaker Model Wiring Sensor Rating Product Number GO-104P
225 AK-1-15 3 Wire 150A PK115D3F0108 緯軒機電2550.00
225 AK-1-15 3 Wire 225A PK115D3F0208 緯軒機電2550.00
225 AK-1-15 4 Wire 150A PK115D4F0108 緯軒機電2775.00
225 AK-1-15 4 Wire 225A PK115D4F0208 緯軒機電2775.00
225 AK-15 3 Wire 150A PKO15D3F0108 緯軒機電2550.00
225 AK-15 3 Wire 225A PKO15D3F0208 緯軒機電2550.00
225 AK-15 4 Wire 150A PKO15D4F0108 緯軒機電2775.00
225 AK-15 4 Wire 225A PKO15D4F0208 緯軒機電2775.00
600 AK-1-25 3 Wire 150A PK125D3F0108 緯軒機電2550.00
600 AK-1-25 3 Wire 225A PK125D3F0208 緯軒機電2550.00
600 AK-1-25 3 Wire 600A PK125D3F0608 緯軒機電2550.00
600 AK-1-25 4 Wire 150A PK125D4F0108 緯軒機電2775.00
600 AK-1-25 4 Wire 225A PK125D4F0208 緯軒機電2775.00
600 AK-1-25 4 Wire 600A PK125D4F0608 緯軒機電2775.00
600 AK-25, AKU-25 3 Wire 150A PKO25D3F0108 緯軒機電2550.00
600 AK-25, AKU-25 3 Wire 225A PKO25D3F0208 緯軒機電2550.00
600 AK-25, AKU-25 3 Wire 600A PKO25D3F0608 緯軒機電2550.00
600 AK-25, AKU-25 4 Wire 150A PKO25D4F0108 緯軒機電2775.00
600 AK-25, AKU-25 4 Wire 225A PKO25D4F0208 緯軒機電2775.00
600 AK-25, AKU-25 4 Wire 600A PKO25D4F0608 緯軒機電2775.00
1600 AK-1-50 3 Wire 800A PK150D3F0808 緯軒機電2800.00
1600 AK-1-50 3 Wire 1600A PK150D3F1608 緯軒機電2800.00
1600 AK-1-50 4 Wire 800A PK150D4F0808 緯軒機電3025.00
1600 AK-1-50 4 Wire 1600A PK150D4F1608 緯軒機電3025.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 3 Wire 800A PKO50D3F0808 緯軒機電2800.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 3 Wire 1600A PKO50D3F1608 緯軒機電2800.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 3 Wire 2000A PKO50D3F2008 緯軒機電2800.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 4 Wire 800A PKO50D4F0808 緯軒機電3025.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 4 Wire 1600A PKO50D4F1608 緯軒機電3025.00
1600 AK-50, AKU-50, AKT-50, AKS-50, AKSU-50, AKST-50 4 Wire 2000A PKO50D4F2008 緯軒機電3025.00
3000 AK-75 3 Wire 3000A PKO75D3F3008 緯軒機電2800.00
3000 AK-75 4 Wire 3000A PKO75D4F3008 緯軒機電3025.00
4000 AK-100 3 Wire 4000A PKO10D3F4008 緯軒機電3050.00
4000 AK-100 4 Wire 4000A PKO10D4F4008 緯軒機電3275.00
Conversion kits come standard with a rating plug that matches the current sensor. For rating plugs with different values, price and order separaby. See page 2-11.
Switchgear
2
2-8 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
ProTrip? Trip Unit Conversion Kit Selection Guide
For *I-T-E Circuit Breakers
Product Number Structure
PIK22 D 3 F 02 08
Breaker
K225
K600
KD0N600
K800
?KD0N800
?K1600 (black)
?KD0N1600 (black)
?K1600 (red)
?KD0N1600 (red)
Wiring
?3 Wire-3
?4 Wire-4
Sensor Type
?Fixed CTs-F
Applicable to breakers originally equipped with either electro-mechanical
trip devices or with solid state trip devices ("S" version breakers).
Only applicable to breakers originally equipped with rectangular shaped
primary disconnect assemblies.
Only applicable to breakers originally equipped with circular shaped
primary disconnect assemblies.
Trip Functions
LSIGX- 08
Trip Unit Functions
LSIGX- Long Time, Short Time/INST.
?and Switchable Ground Fault (off)
?Not Approved for a UL Listed Breaker
Model
Generation-D
Sensor Rating
150A- 01
?225A- 02
?400A- 04
?600A- 06
?800A- 08
?1600A- 16
Sensor Rating Selection
?Frame Breaker Product Numbers Sensors
PIK221
PIK601
PIK801
PIK1B1
PIK161,2
PIKN1,3
225 K225 150A, 225A
600 K600, KD0N600 150A, 225A, 600A
800 K800, KD0N800 150A, 400A, 800A
?K1600 (black),
1600 KD0N1600 (black), 800A, 1600A
?K1600 (red), KD0N1600 (red)
1
2
3
ProTrip? Conversion Kits
List Price
Frame Size (Amps) Breaker Model Wiring Sensor Rating Product Number GO-104P
225 K225 3 Wire 150A PIK22D3F0108 緯軒機電2450.00
225 K225 3 Wire 225A PIK22D3F0208 緯軒機電2450.00
225 K225 4 Wire 150A PIK22D4F0108 緯軒機電2675.00
225 K225 4 Wire 225A PIK22D4F0208 緯軒機電2675.00
600 K600, KDON600 3 Wire 150A PIK60D3F0108 緯軒機電2350.00
600 K600, KDON600 3 Wire 225A PIK60D3F0208 緯軒機電2350.00
600 K600, KDON600 3 Wire 600A PIK60D3F0608 緯軒機電2350.00
600 K600, KDON600 4 Wire 150A PIK60D4F0108 緯軒機電2575.00
600 K600, KDON600 4 Wire 225A PIK60D4F0208 緯軒機電2575.00
600 K600, KDON600 4 Wire 600A PIK60D4F0608 緯軒機電2575.00
800 K800, KDON800 3 Wire 150A PIK80D3F0108 緯軒機電2350.00
800 K800, KDON800 3 Wire 400A PIK80D3F0408 緯軒機電2350.00
800 K800, KDON800 3 Wire 800A PIK80D3F0808 緯軒機電2350.00
800 K800, KDON800 4 Wire 150A PIK80D4F0108 緯軒機電2575.00
800 K800, KDON800 4 Wire 400A PIK80D4F0408 緯軒機電2575.00
800 K800, KDON800 4 Wire 800A PIK80D4F0808 緯軒機電2575.00
1600 K1600 (black), KDON1600 (black) 3 Wire 800A PIK1BD3F0808 緯軒機電2700.00
1600 K1600 (black), KDON1600 (black) 3 Wire 1600A PIK1BD3F1608 緯軒機電2700.00
1600 K1600 (black), KDON1600 (black) 4 Wire 800A PIK1BD4F0808 緯軒機電2925.00
1600 K1600 (black), KDON1600 (black) 4 Wire 1600A PIK1BD4F1608 緯軒機電2925.00
1600 K1600 (red) 3 Wire 800A PIK16D3F0808 緯軒機電2700.00
1600 K1600 (red) 3 Wire 1600A PIK16D3F1608 緯軒機電2700.00
1600 K1600 (red) 4 Wire 800A PIK16D4F0808 緯軒機電2925.00
1600 K1600 (red) 4 Wire 1600A PIK16D4F1608 緯軒機電2925.00
1600 KDON1600 (red) 3 Wire 800A PIKN1D3F0808 緯軒機電2700.00
1600 KDON1600 (red) 3 Wire 1600A PIKN1D3F1608 緯軒機電2700.00
1600 KDON1600 (red) 4 Wire 800A PIKN1D4F0808 緯軒機電2925.00
1600 KDON1600 (red) 4 Wire 1600A PIKN1D4F1608 緯軒機電2925.00
Conversion kits come standard with a rating plug that matches the current sensor. For rating plugs with different values, price and order separaby. See page 2-11.
*I-T-E is a registered trademark of Siemens Energy and Automation, Inc.
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-9
to change without notice
Low Voltage Power and DC Circuit Breakers
ProTrip? Trip Unit Conversion Kit Selection Guide
For *Allis-Chalmers Circuit Breakers
Product Number Structure
PSL6B 3 F 02 08 D
Breaker
LA-600 (blue)
LAF-600 (blue)
LA-600 (gold)
LAF-600 (gold)
LA-800 (gold)
LAF-800 (gold)
?LA-1600 (blue)
LAF-1600 (blue)
?LA-1600 (gold)
LAF-1600 (gold)
Wiring
?3 Wire-3
?4 Wire-4
Sensor Type
?Fixed CTs-F
Trip Functions
LSIGX- 08
Trip Unit Functions
LSIGX- Long Time, Short Time/INST.
?and Switchable Ground Fault (off)
?Not Approved for a UL Listed Breaker
Model
Generation-D
Sensor Rating
150A- 01
?225A- 02
?400A- 04
?600A- 06
?800A- 08
?1600A- 16
Sensor Rating Selection
?Frame Breaker Product Numbers Sensors
?LA-600 (blue), LAF-600 (blue)
?LA-600 (gold), LAF-600 (gold)
?LA-800 (gold), LAF-800 (gold)
?LA-1600 (blue), LAF-1600 (blue)
?LA-1600 (gold), LAF-1600 (gold)
PSL6B
PSL6G
PSL8O
PSL1B
PSL1G
600
800
1600
150A, 225A, 600A
150A, 400A, 800A
800A, 1600A
ProTrip? Conversion Kits
List Price
Frame Size (Amps) Breaker Model Wiring Sensor Rating Product Number GO-104P
600 LA-600 (blue), LAF-600 (blue) 3 Wire 150A PSL6BD3F0108 緯軒機電2350.00
600 LA-600 (blue), LAF-600 (blue) 3 Wire 225A PSL6BD3F0208 緯軒機電2350.00
600 LA-600 (blue), LAF-600 (blue) 3 Wire 600A PSL6BD3F0608 緯軒機電2350.00
600 LA-600 (blue), LAF-600 (blue) 4 Wire 150A PSL6BD4F0108 緯軒機電2575.00
600 LA-600 (blue), LAF-600 (blue) 4 Wire 225A PSL6BD4F0208 緯軒機電2575.00
600 LA-600 (blue), LAF-600 (blue) 4 Wire 600A PSL6BD4F0608 緯軒機電2575.00
600 LA-600 (gold), LAF-600 (gold) 3 Wire 150A PSL6GD3F0108 緯軒機電2350.00
600 LA-600 (gold), LAF-600 (gold) 3 Wire 225A PSL6GD3F0208 緯軒機電2350.00
600 LA-600 (gold), LAF-600 (gold) 3 Wire 600A PSL6GD3F0608 緯軒機電2350.00
600 LA-600 (gold), LAF-600 (gold) 4 Wire 150A PSL6GD4F0108 緯軒機電2575.00
600 LA-600 (gold), LAF-600 (gold) 4 Wire 225A PSL6GD4F0208 緯軒機電2575.00
600 LA-600 (gold), LAF-600 (gold) 4 Wire 600A PSL6GD4F0608 緯軒機電2575.00
800 LA-800 (gold) 3 Wire 150A PSL80D3F0108 緯軒機電2500.00
800 LA-800 (gold) 3 Wire 400A PSL80D3F0408 緯軒機電2500.00
800 LA-800 (gold) 3 Wire 800A PSL80D3F0808 緯軒機電2500.00
800 LA-800 (gold) 4 Wire 150A PSL80D4F0108 緯軒機電2725.00
800 LA-800 (gold) 4 Wire 400A PSL80D4F0408 緯軒機電2725.00
800 LA-800 (gold) 4 Wire 800A PSL80D4F0808 緯軒機電2725.00
1600 LA-1600 (blue), LAF-1600 (blue) 3 Wire 800A PSL1BD3F0808 緯軒機電2700.00
1600 LA-1600 (blue), LAF-1600 (blue) 3 Wire 1600A PSL1BD3F1608 緯軒機電2700.00
1600 LA-1600 (blue), LAF-1600 (blue) 4 Wire 800A PSL1BD4F0808 緯軒機電2925.00
1600 LA-1600 (blue), LAF-1600 (blue) 4 Wire 1600A PSL1BD4F1608 緯軒機電2925.00
1600 LA-1600 (gold), LAF-1600 (gold) 3 Wire 800A PSL1GD3F0808 緯軒機電2700.00
1600 LA-1600 (gold), LAF-1600 (gold) 3 Wire 1600A PSL1GD3F1608 緯軒機電2700.00
1600 LA-1600 (gold), LAF-1600 (gold) 4 Wire 800A PSL1GD4F0808 緯軒機電2925.00
1600 LA-1600 (gold), LAF-1600 (gold) 4 Wire 1600A PSL1GD4F1608 緯軒機電2925.00
Conversion kits come standard with a rating plug that matches the current sensor. For rating plugs with different values, price and order separaby. See page 2-11.
*Allis-Chalmers is a trademark of Allis-Chalmers Manufacturing Company Corporation.
Switchgear
2
2-10 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
ProTrip? Trip Unit Conversion Kit Selection Guide
For *Westinghouse Circuit Breakers
Product Number Structure
PDB15 3 F 02 08 D
Breaker
DB15, DBL15- PDB15
DB25, DBL25- PDB25
DB50, DBL50- PDB50
DB75- PDB75
DB100- PDB10
Wiring
?3 Wire-3
?4 Wire-4
Sensor Type
?Fixed CTs-F
Trip Functions
LSIGX- 08
Trip Unit Functions
LSIGX- Long Time, Short Time/INST.
?and Switchable Ground Fault (off)
?Not Approved for a UL Listed Breaker
Model
Generation-D
Sensor Rating
150A- 01
?225A- 02
?600A- 06
?800A- 08
?1600A- 16
?3000A- 30
?4000A- 40
Sensor Rating Selection
?Frame Breaker Product Numbers Sensors
?225 DB15, DBL15 150A, 225A
?600 DB25, DBL25 225A, 600A
?1600 DB50, DBL50 800A,1600A
?3000 DB75 3000A
?4000 DB100 4000A
ProTrip? Conversion Kits
List Price
Frame Size (Amps) Breaker Model Wiring Sensor Rating Product Number GO-104P
225 DB15, DBL15 3 Wire 150A PDB15D3F0108 緯軒機電2250.00
225 DB15, DBL15 3 Wire 225A PDB15D3F0208 緯軒機電2250.00
225 DB15, DBL15 4 Wire 150A PDB15D4F0108 緯軒機電2475.00
225 DB15, DBL15 4 Wire 225A PDB15D4F0208 緯軒機電2475.00
600 DB25, DBL25 3 Wire 150A PDB25D3F0108 緯軒機電2350.00
600 DB25, DBL25 3 Wire 225A PDB25D3F0208 緯軒機電2350.00
600 DB25, DBL25 3 Wire 600A PDB25D3F0608 緯軒機電2350.00
600 DB25, DBL25 4 Wire 150A PDB25D4F0108 緯軒機電2575.00
600 DB25, DBL25 4 Wire 225A PDB25D4F0208 緯軒機電2575.00
600 DB25, DBL25 4 Wire 600A PDB25D4F0608 緯軒機電2575.00
1600 DB50, DBL50 3 Wire 800A PDB50D3F0808 緯軒機電2350.00
1600 DB50, DBL50 3 Wire 1600A PDB50D3F1608 緯軒機電2350.00
1600 DB50, DBL50 4 Wire 800A PDB50D4F0808 緯軒機電2575.00
1600 DB50, DBL50 4 Wire 1600A PDB50D4F1608 緯軒機電2575.00
3000 DB75 3 Wire 3000A PDB75D3F3008 緯軒機電2600.00
3000 DB75 4 Wire 3000A PDB75D4F3008 緯軒機電2825.00
4000 DB100 3 Wire 4000A PDB10D3F4008 緯軒機電2850.00
4000 DB100 4 Wire 4000A PDB10D4F4008 緯軒機電3075.00
Conversion kits come standard with a rating plug that matches the current sensor. For rating plugs with different values, price and order separaby. See page 2-11.
*Westinghouse is a trademark of Westinghouse Electric Corporation.
Switchgear
2
Prices and data subject Aftermarket Catalog www.geelectrical.com 2-11
to change without notice
*I-T-E is a registered trademark of Siemens Energy and Automation, Inc.
*Westinghouse is a trademark of Westinghouse Electric Corporation.
*Allis-Chalmers is a trademark of Allis-Chalmers Manufacturing Company Corporation.
Low Voltage Power and DC Circuit Breakers
ProTrip? Rating Plugs
ProTrip? conversion kits come standard with a rating plug that
matches the current sensor. For rating plugs with different values,
price and order separaby.
Rating Plug
Reference Publications
ProTrip? Trip Unit Conversion Kits for
GE Power Circuit Breakers - Fact Sheet DET-228
ProTrip? Trip Unit Conversion Kits for
*Westinghouse Power Circuit Breakers - Fact Sheet DET-230
ProTrip? Trip Unit Conversion Kits for
*Allis-Chalmers Power Circuit Breakers - Fact Sheet DET-231
ProTrip? Trip Unit Conversion Kits for
*I-T-E Power Circuit Breakers - Fact Sheet DET-229
Rating Plugs
List Price
Frame Size (Amps) Sensor Rating (Amps) Current Rating (Amps) Current Range (Amps) Product Number GO-104P
225|600|800 150 80 40-88 PT1C80GFD 緯軒機電149.00
225|600|800 150 100 50-110 PT1C100GFD 緯軒機電149.00
225|600|800 150 125 63-138 PT1C125GFD 緯軒機電149.00
225|600|800 150 150 75-165 PT1C150GFD1 緯軒機電149.00
225|600|800 225 150 75-165 PT225C150GFD 緯軒機電149.00
225|600|800 225 225 113-248 PT225C225GFD1 緯軒機電149.00
600 600 300 150-330 PT6C300GFD 緯軒機電149.00
600 600 400 200-440 PT6C400GFD 緯軒機電149.00
600 600 450 225-495 PT6C450GFD 緯軒機電149.00
600 600 500 250-550 PT6C500GFD 緯軒機電149.00
600 600 600 300-660 PT6C600GFD1 緯軒機電149.00
800 400 200 100-220 PT4C200GFD 緯軒機電149.00
800 400 225 113-248 PT4C225GFD 緯軒機電149.00
800 400 250 125-275 PT4C250GFD 緯軒機電149.00
800 400 300 150-330 PT4C300GFD 緯軒機電149.00
800 400 400 200-440 PT4C400GFD1 緯軒機電149.00
800|1600 800 400 200-440 PT8C400GFD 緯軒機電149.00
800|1600 800 450 225-495 PT8C450GFD 緯軒機電149.00
800|1600 800 500 250-550 PT8C500GFD 緯軒機電149.00
800|1600 800 600 300-660 PT8C600GFD 緯軒機電149.00
800|1600 800 700 350-770 PT8C700GFD 緯軒機電149.00
800|1600 800 800 400-880 PT8C800GFD1 緯軒機電149.00
1600 1600 800 400-880 PT16C800GFD 緯軒機電149.00
1600 1600 1000 500-1100 PT16C1000GFD 緯軒機電149.00
1600 1600 1100 550-1210 PT16C1100GFD 緯軒機電149.00
1600 1600 1200 600-1320 PT16C1200GFD 緯軒機電149.00
1600 1600 1600 800-1760 PT16C1600GFD 緯軒機電149.00
2000 2000 1000 500-1100 PT20C1000GFD 緯軒機電149.00
2000 2000 1200 600-1320 PT20C1200GFD 緯軒機電149.00
2000 2000 1500 750-1650 PT20C1500GFD 緯軒機電149.00
2000 2000 1600 800-1760 PT20C1600GFD 緯軒機電149.00
2000 2000 2000 1000-2200 PT20C2000GFD 緯軒機電149.00
3000 3000 1200 600-1320 PT30C1200GFD 緯軒機電149.00
3000 3000 1600 800-1760 PT30C1600GFD 緯軒機電149.00
3000 3000 2000 1000-2200 PT30C2000GFD 緯軒機電149.00
3000 3000 2500 1250-2750 PT30C2500GFD 緯軒機電149.00
3000 3000 3000 1500-3300 PT30C3000GFD1 緯軒機電149.00
4000 4000 1600 800-1760 PT40C1600GFD 緯軒機電149.00
4000 4000 2000 1000-2200 PT40C2000GFD 緯軒機電149.00
4000 4000 2500 1250-2750 PT40C2500GFD 緯軒機電149.00
4000 4000 3000 1500-3300 PT40C3000GFD 緯軒機電149.00
4000 4000 3600 1800-3960 PT40C3600GFD 緯軒機電149.00
4000 4000 4000 2000-4000 PT40C4000GFD1 緯軒機電149.00
Rating Plug furnished with conversion kit.
Note: Long Time pickup range is 0.5-1.1 times the rating plug value. 1.1 setting allows the breaker to carry 100% of the rating plug current value, not to exceed the
continuous current (frame) rating of the breaker.
Switchgear
2
2-12 Aftermarket Catalog www.geelectrical.com Prices and data subject
to change without notice
Low Voltage Power and DC Circuit Breakers
EnbliGuard? TU Trip Unit
Conversion Kits Selection Guide
Sensor Rating Selection
AKO25 C 3 F 06 04 A
Breaker
AK-1-15 = AK115
AK-15 = AKO151
AK-1-25 = AK125
AK-25
AKU-25 = AKO251
AKR-30
AKR-30H = AKR30
AKRU-30
AKR-30S
AKRU-30S = AKR3S2
AK-1-50 = AK150
AK-50
AKU-503
AKT-50 = AKO501
AKS-50
AKSU-503
AKST-50
AKR-50
AKR-50H
AKRU-50
AKRT-50
AKRT-50H = AKR504
AKJ-50
AKJ-50H
AKJT-50
AKJT-50H
AK-753 = AKO755
AKR-75 = AKR755
AK-1003 = AKO105
AKR-100 = AKR105
AKW-100 = AKW105
Breaker
DB-15 = ADB15
DK-15 = ADK159
DB-25
DBL-25 = ADB25
DK-25 = ADK259
DS-206
DSL-206 = ADS06
DA-50 = ADA509
DB-50
DBL-50 = ADB50
DS-416 = ADS16 DSL-416
DS-420 = ADS20
DS-532 = ADS539
DA-75 = ADA759
DB-75 = ADB75
DS-632 = ADS32
DA-100 = ADA109
DB-100 = ADB10
DS-840 = ADS409
GE ***Westinghouse25 *Allis-Chalmers25 **I-T-E25
Breaker
LA = ASL259
LA-25A = ASL2A9
LA-600(Blue) = ASL6B17,18
LAF-600(Blue) = ASL6B17,18,19
LA-600(Gold) = ASL6G18,20
LAF-600(Gold) = ASL6G18,19,20
LA-50(800A) = ASL589,21
LA-800 = ASL8018,20
LAF-800 = ASL8018,19,20