詳細(xì)參數(shù) | |||
---|---|---|---|
品牌 | Honeywell | 型號(hào) | FS7-2173-2RP |
結(jié)構(gòu)形式 | 模塊式 | 安裝方式 | 控制室安裝 |
LD指令處理器 | 硬PLC | 功能 | 多光譜火災(zāi)和火焰探測(cè)器 |
工作電壓 | 24VDC | 環(huán)境溫度 | 0至70°C |
環(huán)境濕度 | 0到90%的相對(duì)濕度,無(wú)冷凝 | 加工定制 | 否 |
重量 | 3磅 |
Honeywell Analytics FS7-2173-2RP
物品 :FS7-2173-2RP
品牌:霍尼韋爾分析
FS7-2173-2RP FS7 多光譜火災(zāi)和火焰探測(cè)器,非閉鎖警報(bào)和報(bào)警繼電器,Honeywell Analytics 的 Viton O 形圈
Fire Sentry FS7-2173 光電輻射能火災(zāi)探測(cè)器 - 和具有多光譜寬帶 IR?、近帶 IR 和可見(jiàn)帶火災(zāi)探測(cè)功能的 Fire Sentry FS7-2173-2RP(組合型號(hào))專(zhuān)為半導(dǎo)體潔凈室而設(shè)計(jì)防火應(yīng)用。Fire Sentry FS7 火災(zāi)探測(cè)器提供對(duì)半導(dǎo)體濕臺(tái)火災(zāi)的智能兩級(jí)響應(yīng):
第一階段:警報(bào)。這是對(duì)熱能輸出為 3 kW(相當(dāng)于直徑 4 英寸的聚丙烯水池火災(zāi))的小火的第一階段響應(yīng)。這使火有時(shí)間自熄。
階段 2:警報(bào)。如果火不能自熄,并增長(zhǎng)到工廠互助協(xié)會(huì)的 13 kW 熱能閾值(相當(dāng)于 8 英寸直徑的聚丙烯水池火災(zāi)),則激活第二階段響應(yīng)。
Fire Sentry FS7-2173 與 Fire Sentry FS7-130-SX 控制器或控制面板 FSWB 一起使用??刂破骱涂刂泼姘鍨樘綔y(cè)器供電,監(jiān)控所有探測(cè)器的狀態(tài),并通過(guò)數(shù)字 RS-485 通信通道與探測(cè)器進(jìn)行通信。Fire Sentry FS7-2173 配備標(biāo)準(zhǔn)的 20 英尺電纜連接器。探測(cè)器使用自鎖連接器和 Fire Sentry 接線(xiàn)盒連接到控制器或控制面板。這允許快速簡(jiǎn)單的連接,消除接線(xiàn)問(wèn)題。每個(gè)探測(cè)器可以在非易失性存儲(chǔ)器中存儲(chǔ)多達(dá)六個(gè)時(shí)間和日期標(biāo)記的 FirePics?(事件前多光譜傳感器陣列數(shù)據(jù))??刂破骱涂刂泼姘暹€可以將事件歷史表存儲(chǔ)在非易失性存儲(chǔ)器中,其中包含帶有時(shí)間和日期標(biāo)記的警報(bào)、警報(bào)和故障歷史記錄。
Fire Sentry FS7-2173-2RP 單元化型號(hào)的微處理器采用數(shù)字信號(hào)處理算法,持續(xù)監(jiān)控電路、傳感器的內(nèi)置自檢并驗(yàn)證是否正常運(yùn)行。帶有離散繼電器輸出的 Fire Sentry FS7-2173-2RP 設(shè)計(jì)用作獨(dú)立探測(cè)器并與任何經(jīng)批準(zhǔn)的火警面板接口。探測(cè)器需要一個(gè)外部 24 VDC 電源,并配有標(biāo)準(zhǔn)的 20 英尺尾纖電纜。它可以在非易失性存儲(chǔ)器中存儲(chǔ)多達(dá)六個(gè)時(shí)間和日期標(biāo)記的 FirePics? 和 200 個(gè)事件。FirePics? 和事件歷史可以使用 Fire Sentry FS7 接口套件和 Fire Sentry 基于 Windows 的 PC 軟件進(jìn)行檢索。
特征:
多光譜數(shù)字光電輻射能紅外火災(zāi)探測(cè)器
獨(dú)特的兩級(jí)火災(zāi)探測(cè)響應(yīng)
免疫誤報(bào)源
不受吸收煙霧、氣體或化學(xué)蒸氣的影響
對(duì)來(lái)自電加熱器和烤箱的背景輻射能量不
檢測(cè)碳?xì)浠衔锖头翘細(xì)浠衔锘馂?zāi)
堅(jiān)固的防漏、熱密封、耐酸、注塑聚丙烯外殼
120° 寬視野
帶RS-485接口的數(shù)字通訊
FirePic?;帶有時(shí)間和日期戳的數(shù)字火災(zāi)簽名
內(nèi)置探測(cè)器自動(dòng)自檢
單機(jī)操作的單元化模型設(shè)計(jì)
應(yīng)用包括:
潔凈室的開(kāi)放區(qū)域
濕臺(tái)工作面
濕臺(tái)面地下(壓力通風(fēng)系統(tǒng))
位于濕臺(tái)區(qū)后面的泵和設(shè)備
地板下區(qū)域
IPA 工作站(僅限組合型號(hào))
The Fire Sentry FS7-2173 electro-optical radiant energy fire detector - and the Fire Sentry FS7-2173-2RP (unitized model) with multi-spectral WideBand IR?, Near Band IR and Visible Band fire detection are designed specifically for semiconductor Clean Room fire protection applications.The Fire Sentry FS7 fire detector provides and inbligent two-stage response to semiconductor wet bench fires:
Stage 1: Alert. This is the first-stage response to a small fire with a heat energy output of 3 kW (the equivalent of a 4-inch diameter polypropylene pool fire). This allows time for the fire to self-extinguish.
Stage 2: Alarm. If the fire does not self-extinguish, and grows to the Factory Mutual specified heat energy threshold of 13 kW (the equivalent of an 8-inch diameter polypropylene pool fire), the second-stage response is activated.
The Fire Sentry FS7-2173 is used with Fire Sentry FS7-130-SX Controller or Control Panel FSWB. Controller and Control Panel supply power to detectors monitor the status of all detectors and communicate with the detectors via the digital RS-485 communication channel. Fire Sentry FS7-2173 is supplied with a standard 20 ft. cable connector. Detectors are connected to the controller or control panel using the self-locking connectors and Fire Sentry junction boxes. This allows for fast and easy connections eliminating wiring problems. Each detector can store up to six time and date stamped FirePics? (pre-event multi-spectral sensor array data) in non-volatile memory. Controller and control panel can also store event history table in the non-volatile memory, which contains the time and date stamped alert, alarm and fault histories. FirePics? and event histories can be retrieved from the controller or control panel.
Fire Sentry FS7-2173-2RP unitized model's microprocessor, with digital signal processing algorithms, continuously monitors the circuitry, sensor's built-in selftest and verifies proper operation. Fire Sentry FS7-2173-2RP with discrete relay outputs is designed to operate as a stand-alone detector and interface with any approved fire alarm panel. The detector requires an external 24 VDC power source and is supplied with a standard 20 ft. pigtail cable. It can store up to six time and date stamped FirePics? and 200 events in non-volatile memory. FirePics? and event histories can be retrieved using a Fire Sentry FS7 Interface Kit and the Fire Sentry Windows-based PC software.