西門子6AG1315-2EH14-2AY0
西門子SIPLUS CPU315-2PN/DP
銷售訂貨號:
![]() |
6AG1315-2EH14-2AY0
SIPLUS S7-300 CPU315-2PN/DP -25 ... +60 DEGREES C WITH CONFORMITY TO EN50155 T1 CAT 1 CL A/B BASED ON 6ES7315-2EH14-0AB0 . CENTRAL PROCESSING UNIT WITH 384 KBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, MICRO MEMORY CARD NECESSARY
|
![]() |
6AG1315-2EH14-7AB0
SIPLUS S7-300 CPU315-2PN/DP -25 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7315-2EH14-0AB0 . CENTRAL PROCESSING UNIT WITH 384 KBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, MICRO MEMORY CARD NECESSARY
|
西門子S7-300PLC 優(yōu)勢價格 現(xiàn)貨銷售
聯(lián)系人 :卜社幫( 銷售經(jīng)理 )24小時服務(wù)熱線 :18202105796
電話( Tel ): 021-60641323 傳真(Fax):021-57872917
工作QQ: 2880583563
地址( Add ):上海市松江區(qū)弘翔路58弄195號
CPU 的運(yùn)行需要 SIMATIC 微型存儲卡。
該 CPU 具有中等容量程序存儲器和數(shù)量框架
二進(jìn)制和浮點運(yùn)算處理性能高
在具有集中式和分布式 I/O 的生產(chǎn)線上作為集中式控制器使用
經(jīng)由 PROFINET 的基于組件的自動化 (CBA)
PROFINET 代理,用于基于組件的自動化(CBA)中的 PROFIBUS DP 智能設(shè)備
PROFINET I/O 控制器,用于在 PROFINET 上運(yùn)行分布式 I/O
用于 2 端口交換機(jī)的 PROFINET 接口
組合式 MPI/PROFIBUS DP 主站/從站接口
在PROFIBUS上實現(xiàn)等時同步模式
注:
SIPLUS extreme 產(chǎn)品基于 SIMATIC 標(biāo)準(zhǔn)產(chǎn)品。此處的內(nèi)容摘自相關(guān)的標(biāo)準(zhǔn)產(chǎn)品。增加了與 SIPLUS extreme 相關(guān)的信息
CPU 315-2 PN/DP 具有中等規(guī)模程序量.除了分布式I/O結(jié)構(gòu),它還可用于分布式自動化結(jié)構(gòu)。可在SIMATIC S7-300中用作PROFINET IO控制器以及標(biāo)準(zhǔn)PROFIBUS DP主站。CPU 315-2 PN/DP還可用作分布式智能從站(DP從站)。
CPU 315-2 PN/DP為采用軟件來實現(xiàn)一些簡單的工藝任務(wù)提供了一個理想的平臺,例如:
Easy Motion Control 運(yùn)動控制
使用 STEP 7 塊或運(yùn)行軟件“標(biāo)準(zhǔn)/模塊化PID控制” 來實現(xiàn)閉環(huán)控制任務(wù)的解決方案
使用 SIMATIC S7-PDIAG 進(jìn)行擴(kuò)展過程診斷。
無需其他組件,通過CPU的集成組合就可以實現(xiàn)網(wǎng)絡(luò)自動化解決方案。
CPU 315-2 PN/DP 裝配有:
微處理器;
處理器處理每條二進(jìn)制指令執(zhí)行時間約為 50 ns,每條浮點數(shù)運(yùn)行指令約為 450ns。
384 KB 主存儲器(相當(dāng)于大約 128 K 條指令);
與程序組件執(zhí)行相關(guān)的大容量工作存儲器為用戶程序提供了充分的空間。作為程序裝載存儲器的微型存儲卡(最大為 8 MB)也允許將可以項目(包括符號和注釋)保存在 CPU 中。裝載存儲器還可用于數(shù)據(jù)歸檔和配方管理。
靈活的擴(kuò)展;
多達(dá) 32 個模塊,(4 層結(jié)構(gòu))
MPI/DP 組合接口;
第一個集成的 MPI/DP 接口最多能同時建立 16 個與 S7-300/400的連接或與編程器、PC 和 OP 的連接。 在這些連接中,始終分別為 PG 和 OP 各保留一個連接。
MPI 可以通過“全局?jǐn)?shù)據(jù)通訊”與最多32個CPU組建簡單的網(wǎng)絡(luò)。
該接口可從MPI接口重新設(shè)置為DP接口。
PROFIBUS DP 接口:
DP 接口可用作 DP 主站或 DP 從站運(yùn)行。在該接口上,PROFIBUS DP從站可在等時模式下運(yùn)行.全面支持 PROFIBUS DP V1 標(biāo)準(zhǔn)。這將增加 DP V1 標(biāo)準(zhǔn)從站在診斷和參數(shù)賦值能力的范圍。
以太網(wǎng)接口;
CPU 315-2 PN/DP 的第 2 個內(nèi)置接口是一個基于以太網(wǎng) TCP/IP 的 PROFINET 接口,帶有雙端口交換機(jī)。
它支持下列協(xié)議:
S7通訊用于在SIMATIC控制器間進(jìn)行數(shù)據(jù)通訊;
通過 STEP 7 進(jìn)行編程、啟動和診斷的 PG/OP 通訊;
與HMI和SCADA連接的PG/OP通訊;
在PROFINET上實現(xiàn)開放的TCP/IP、UDP和ISO-on-TCP (RFC1006)通訊;
SIMATIC NET OPC-Server用于與其它控制器以及CPU自帶的I/O設(shè)備進(jìn)行通訊
口令保護(hù);
用戶程序使用密碼保護(hù),可防止非法訪問。
診斷緩沖;
最后500個故障和中斷事件保存在該緩沖區(qū)中,供診斷使用。
免維護(hù)的數(shù)據(jù)后備;
在電源恢復(fù)后,CPU 自動保存所有數(shù)據(jù)(最大128KB),當(dāng)重新上電后,可繼續(xù)保留這些數(shù)據(jù)。
可參數(shù)化的特性
可以使用 STEP 7 對 S7 的組態(tài)、屬性以及CPU的響應(yīng)進(jìn)行參數(shù)設(shè)置:
MPI多點接口;
定義站地址
啟動;
定義 CPU 的啟動特性
同步循環(huán)中斷;
設(shè)置 DP 主站系統(tǒng)、過程映像分區(qū)編號和延時時間
循環(huán)/時鐘存儲器;
指定最大循環(huán)時間和負(fù)載。設(shè)置時鐘存儲器地址
保持性;
設(shè)置保持區(qū)
時鐘中斷;
設(shè)定起始日期、起始時間和間隔周期
看門狗中斷;
周期設(shè)定
系統(tǒng)診斷;
定義診斷報警的處理和范圍
時鐘;
設(shè)定AS內(nèi)或MPI上的同步類型
防護(hù)等級;
定義程序和數(shù)據(jù)的訪問權(quán)限
通訊;
保留連接源
Web;
CPU 的 Web 服務(wù)器設(shè)置
PROFIBUS DP 主站/從站接口;
為分布式 I/O 分配用戶地址。
PROFINET 接口;
使用 NTP 處理時間同步參數(shù)
顯示功能與信息功能
狀態(tài)和故障指示;
發(fā)光二極管顯示,例如,硬件、編程、定時器、I/O、總線故障以及運(yùn)行狀態(tài),如RUN、STOP、Startup。
測試功能;
可使用編程器顯示程序執(zhí)行過程中的信號狀態(tài),可以不通過用戶程序而修改過程變量,以及輸出堆棧內(nèi)容。
信息功能;
通過編程器以文本形式為用戶提供存儲能力信息、CPU的運(yùn)行模式,以及工作存儲器和裝載存儲器當(dāng)前的使用情況、當(dāng)前的循環(huán)時間和診斷緩沖區(qū)的內(nèi)容。
集成的通訊功能
編程器/OP 通訊
全局?jǐn)?shù)據(jù)通訊
S7 基本通訊
S7 通訊
S5可兼容通訊
路由
數(shù)據(jù)記錄路由
PROFIBUS DP 主站/從站
通過 TCP/IP、ISO-on-TCP 和 UDP 進(jìn)行開放式通訊
PROFINET IO 控制器
PROFINET CBA(基于組件的自動化)
Web 服務(wù)器
系統(tǒng)功能
CPU 具有廣泛的系統(tǒng)功能特性,諸如:診斷、參數(shù)賦值、報警、定時和測量等。
詳細(xì)信息請參見手冊。
西門子6AG1315-2EH14-2AY0 西門子SIPLUS CPU315-2PN/DP 技術(shù)參數(shù):
Order number |
6AG1315-2EH14-2AY0 |
6AG1315-2EH14-7AB0 |
|
---|---|---|---|
SIPLUS S7-300 CPU315-2PN/DP EN50155 |
SIPLUS S7-300 CPU315-2PN/DP |
||
General information |
|
|
|
Engineering with |
|
|
|
|
STEP7 V 5.5 or higher |
STEP7 V 5.5 or higher |
|
Supply voltage |
|
|
|
Rated value (DC) |
|||
|
Yes |
Yes |
|
Power loss |
|
|
|
Power loss, typ. |
4.65 W |
4.65 W |
|
Memory |
|
|
|
Work memory |
|
|
|
|
384 kbyte |
384 kbyte |
|
|
128 kbyte |
128 kbyte |
|
Load memory |
|
|
|
|
8 Mbyte |
8 Mbyte |
|
CPU processing times |
|
|
|
for bit operations, typ. |
0.05 μs |
0.05 μs |
|
for word operations, typ. |
0.09 μs |
0.09 μs |
|
for fixed point arithmetic, typ. |
0.12 μs |
0.12 μs |
|
for floating point arithmetic, typ. |
0.45 μs |
0.45 μs |
|
Counters, timers and their retentivity |
|
|
|
S7 counter |
|
|
|
|
256 |
256 |
|
IEC counter |
|
|
|
|
Yes |
Yes |
|
S7 times |
|
|
|
|
256 |
256 |
|
IEC timer |
|
|
|
|
Yes |
Yes |
|
Data areas and their retentivity |
|
|
|
Flag |
|
|
|
|
2 048 byte |
2 048 byte |
|
Address area |
|
|
|
I/O address area |
|
|
|
|
2 048 byte |
2 048 byte |
|
|
2 048 byte |
2 048 byte |
|
Process image |
|
|
|
|
2 048 byte |
2 048 byte |
|
|
2 048 byte |
2 048 byte |
|
Time of day |
|
|
|
Clock |
|
|
|
|
Yes |
Yes |
|
Operating hours counter |
|
|
|
|
1 |
1 |
|
1. Interface |
|
|
|
Interface type |
Integrated RS 485 interface |
Integrated RS 485 interface |
|
Physics |
RS 485 |
RS 485 |
|
Functionality |
|
|
|
|
Yes |
Yes |
|
|
Yes |
Yes |
|
|
Yes |
Yes |
|
|
No |
No |
|
DP master |
|
|
|
|
124 |
124 |
|
2. Interface |
|
|
|
Interface type |
PROFINET |
PROFINET |
|
Physics |
Ethernet RJ45 |
Ethernet RJ45 |
|
Interface types |
|
|
|
|
2 |
2 |
|
Functionality |
|
|
|
|
No |
No |
|
|
No |
No |
|
|
No |
No |
|
|
Yes; Also simultaneously with IO-Device functionality |
Yes; Also simultaneously with IO-Device functionality |
|
|
Yes; Also simultaneously with IO Controller functionality |
Yes; Also simultaneously with IO Controller functionality |
|
|
Yes |
Yes |
|
Isochronous mode |
|
|
|
Isochronous operation (application synchronized up to terminal) |
Yes; Via PROFIBUS DP or PROFINET interface |
Yes; Via PROFIBUS DP or PROFINET interface |
|
Communication functions |
|
|
|
PG/OP communication |
Yes |
Yes |
|
Data record routing |
Yes |
Yes |
|
Global data communication |
|
|
|
|
Yes |
Yes |
|
S7 basic communication |
|
|
|
|
Yes |
Yes |
|
S7 communication |
|
|
|
|
Yes |
Yes |
|
S5 compatible communication |
|
|
|
|
Yes; via CP and loadable FC |
Yes; via CP and loadable FC |
|
Open IE communication |
|
|
|
|
Yes; via integrated PROFINET interface and loadable FBs |
Yes; via integrated PROFINET interface and loadable FBs |
|
|
8 |
8 |
|
|
Yes; via integrated PROFINET interface and loadable FBs |
Yes; via integrated PROFINET interface and loadable FBs |
|
|
8 |
8 |
|
|
Yes; via integrated PROFINET interface and loadable FBs |
Yes; via integrated PROFINET interface and loadable FBs |
|
|
8 |
8 |
|
Web server |
|
|
|
|
Yes |
Yes |
|
Number of connections |
|
|
|
|
16 |
16 |
|
Ambient conditions |
|
|
|
Ambient temperature during operation |
|
|
|
|
-25 °C; = Tmin |
-25 °C; = Tmin |
|
|
60 °C; = Tmax; the rated temperature range of -25 ... +55 °C (T1) applies for the use on railway vehicles according to EN50155 |
70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use |
|
Ambient temperature during storage/transportation |
|
|
|
|
-40 °C |
-40 °C |
|
|
70 °C |
70 °C |
|
Extended ambient conditions |
|
|
|
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
|
Relative humidity |
|
|
|
|
100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
|
Resistance |
|
|
|
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! |
|
|
Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
|
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
|
Configuration |
|
|
|
Programming |
|
|
|
Programming language |
|
|
|
|
Yes |
Yes |
|
|
Yes |
Yes |
|
|
Yes |
Yes |
|
|
Yes |
Yes |
|
|
Yes |
Yes |
|
|
Yes |
Yes |
|
|
Yes |
Yes |
|
Know-how protection |
|
|
|
|
Yes |
Yes |
|
|
Yes; With S7 block Privacy |
Yes; With S7 block Privacy |
|
Dimensions |
|
|
|
Width |
40 mm |
40 mm |
|
Height |
125 mm |
125 mm |
|
Depth |
130 mm |
130 mm |
|
Weights |
|
|
|
Weight, approx. |
340 g |
340 g |